Finder Overvoltage protection for sub-distribution Surge arresters 1phase + spark gap IP20 7P.22.8.275.1020 数据表

产品代码
7P.22.8.275.1020
下载
页码 22
2
7P.03.8.260.1025
7P.04.8.260.1025
7P.05.8.260.1025
SPD Type 1+2
3 x combination of varistor 
and encapsulated spark gap 
+ 1 encapsulated spark gap
Visual fault and remote contact
fault signalling varistor/GDT status, 
N-PE GDT presence
Upside down mounting position
Replaceable modules
SPD Type 1+2
3 x combination of varistor 
and encapsulated spark gap
Visual fault and remote contact
fault signalling varistor/GDT status
Upside down mounting position
Replaceable modules
SPD Type 1+2
4 x combination of varistor 
and encapsulated spark gap
Visual fault and remote contact
fault signalling varistor/GDT status
Upside down mounting position
Replaceable modules
SPD specification
Nominal voltage (U
N
)
V  AC
Maximum operating voltage (U
C
)
V  AC
Lightning impulse current (10/350 μs) (I
imp
) kA
Nominal discharge current (8/20 μs) (I
n
)
kA
Maximum discharge current (8/20 μs) (I
max
)kA
Voltage protection level (U
P
)
kV
Ability to independently switch off the 
following current (I
fi
)
Response time (t
a
)
ns
Short-circuit proof at maximum overcurrent protection kA
rms
Maximum overcurrent protection
Maximum overcurrent protection for serial connection
Replacement modules code
Other technical data
Ambient temperature range
°C
Protection degree
Wire size
mm
2
AWG
Wire strip length
mm
Screw torque
Nm
Remote status signalling contact specification
Contact configuration
Rated current
A AC/DC
Rated voltage
V AC/DC
Wire size (07P.01)
mm
2
AWG
Approvals (according to type)
Features
SPD Type 1+2 Surge arrester range - three phase
high discharge capability and without following 
current - system (230/400 V)
Surge arresters, suitable for low-voltage applications,
to protect equipment against overvoltage by direct
lightning strike, induction overvoltage and 
switching overvoltage
To be installed at the boundary of LPZ 0 - LPZ 1 zones or higher
Versions with combined high energy varistor 
block and heavy duty encapsulated spark gap (GDT)
which eliminates leakage current and ensures 
high discharge current
No follow current
Very low residual voltage
Low U
p
voltage
Replaceable modules
Upside down mounting possible (thanks to dual 
terminal markings and new restraint system for 
the replaceable module that permits its inversion)
Visual fault signalling: Healty/Replace
Double screw terminal
Remote status signalling contact: 
Healty/Replace/Presence. Connector  07P.01 included
According to EN 61 643-11
35 mm rail EN 60715 mounting, 36mm each pole
7P.03.8.260.1025 SPD Type 1+2 for three phase 
system without Neutral 
(PEN conductor). Varistor + GDT 
protection L1, L2, L3-PEN
7P.04.8.260.1025 SPD Type 1+2 for three phase 
system with Neutral. Varistor + 
GDT protection L1, L2, L3-N + 
spark gap protection N-PE
7P.05.8.260.1025 SPD Type 1+2 for three phase 
system with Neutral. Varistor + 
GDT protection L1, L2, L3-N +
varistor + GDT protection N-PE
7P Series - Surge Protection Device (SPD)
L-PEN
L-N
N-PE
L, N-PE
230
230
230
260
260
255 260
25
25
100
25
30
30
100
30
60
60
100
60
1.5
1.5
1.5
1.5
No following
No following
100
No following
current
current
current
100
100
100
100
50
50
50
250 A gL/gG
250 A gL/gG
250 A gL/gG
125 A gL/gG
125 A gL/gG
125 A gL/gG
7P.00.8.260.0025
7P.00.8.260.0025 7P.00.1.000.0100
7P.00.8.260.0025
–40...+80
IP20
solid cable
stranded cable
1X2.5...1x50
1X2.5...1x35
1X13...1x1
1X13...1x2
11
4
1 CO (SPDT)
1 CO (SPDT)
1 CO (SPDT)
0.5 - 0.1           
0.5 - 0.1
0.5 - 0.1
250
250
250
solid cable
stranded cable
solid cable
stranded cable
solid cable
stranded cable
1.5
1.5
1.5
1.5
1.5
1.5
16
16
16
16
16
16
For outline drawing see page 11, 12
XII-2012, www
.finder
net.com