Nov 14, 2013    3 / 9
Technical data
Connection (protective circuit, power supply)
Connection type IN
PLUGTRAB plug-in system
Connection type OUT
PLUGTRAB plug-in system
Standards (protective circuit, power supply)
Standards/regulations
IEC 61643-1
Standards/regulations
EN 61643-11
Protective circuit, information technology
Nominal voltage U
N
24 V AC
Max. operating voltage U
max
28 V AC
Max. operating voltage U
max
40 V DC
Arrester rated voltage U
C
40 V DC
Arrester rated voltage U
C
28 V AC
Arrester rated voltage U
C
 (Core-Earth)
40 V DC
Arrester rated voltage U
C
 (Core-Earth)
28 V AC
Nominal current I
N
450 mA (45°C)
Operating effective current I
C
 at U
C
≤ 5 µA
Residual current I
PE
≤ 2 µA
Nominal discharge current I
n
 (8/20) µs (Core-Core)
10 kA
Nominal discharge current I
n
 (8/20) µs (Core-Earth)
10 kA
Max. discharge current I
max
 (8/20) µs maximum (Core-Core)
10 kA
Max. discharge current I
max
 (8/20) µs maximum (Core-Earth)
10 kA
Voltage protection level U
P
 (Core-Core)
≤ 80 V (C2 (10 kV/5 kA))
Voltage protection level U
P
 (Core-Earth)
≤ 450 V (C2 (10 kV/5 kA))
Response time tA (Core-Core)
≤ 1 ns
Response time tA (Core-Earth)
≤ 100 ns
Input attenuation aE, sym.
0.5 dB (≤ 1.5 MHz)
Input attenuation aE, sym.
0.2 dB (≤ 500 kHz / 150 Ω)
Input attenuation aE, sym.
0.1 dB (≤ 100 kHz / 600 Ω)
Cut-off frequency fg (3 dB), sym. in 50 Ohm system
typ. 8 MHz
Cut-off frequency fg (3 dB), sym. in 150 Ohm system
typ. 3 MHz
Cut-off frequency fg (3 dB), sym. in 600 Ohm system
typ. 800 kHz
Capacity (Core-Core)
1.1 nF
Resistance in series
2.2 Ω
Impulse discharge current (10/350) µs, peak value l
imp
2.5 kA
Message: Surge protection fault
Optical, remote indicator contact
Output voltage limitation at 1 kV/µs (wire-wire)
≤ 55 V
Output voltage limitation at 1 kV/µs (wire-earth)
≤ 25 V
Residual voltage at I
n
, (conductor-conductor)
≤ 55 V
Residual voltage with Ian (10/1000)µs (conductor-conductor)
≤ 65 V
Surge carrying capacity in acc. with IEC 61643-21 (Core-Core) C2 (10 kV/5 kA)
Surge carrying capacity in acc. with IEC 61643-21 (Core-Earth) C2 (10 kV/5 kA)