Entes Electricity meter (AC) analogue 32 A ES-32LS ES-32LS 产品宣传页

产品代码
ES-32LS
下载
页码 1
WATT-HOUR METER with RS-485 COMMUNICATION (SINGLE PHASE)
ES-32LS
A6445/Rev.1
Front Panel
Connection Diagram
Neutral Output
Neutral Input
GND
A
Counter
Pulse LED
Phase Output
Phase Input
6+1 digit (000000,0 kWh)
N
L
GND
A
3
6
4
1
Load
phase input
phase output
Neutral Output
Neutral Input
B
B
RS-485
RS-485
By flashing, the LED on the front panel makes it possible toobserve whether the
measuring is active or not.
The LCD display on the front panel makes easy and accurate power reading possible.
Note: User can not reset index. If the value of index exceed 999999.9, it is resetted
automatically and continue to count.
Watt-Hour Meter with LCD
In today's world, Efficient Power Management is very important for low-cost. Measuring process must
have been fulfilled with certain accuracy for precise analysing and measuring the energy.
ES-32LS measures the active watt hour consumption directly and error free in single phase systems
and it shows the total watt hour consumption.
The most important features of the device are its reliability, small size, light weight, modern design, and
easy installation.
247 5 2
Address
Baud
Parity
Adres R/W Definition
Range
Factory settings
1
R/W Modbus address
1-247
1-100
*
2
R/W Baud rate
0:1200, 1:2400, 2:4800,
3:9600, 4:19200, 5:38400
3
3
R/W Parity
0:No, 1:Odd, 2:Even
0
4
R
Index
(High 16 bit)(Wh)
0-15258
0
5
R
Index
(Low 16 bit)(Wh)
0-65535
0
6
R
Voltage (100xV)
0-65535
-
7
R
Current (mA)
0-65535
-
ModBus register adress:
Technical Specifications
Dimensions:
Some applications of ES-32LS are:
Factories
Shopping Malls
Airports
Railway Stations
Stores
Building Complexes
Hotels
Hospitals
Schools
Holiday Villages
Marinas
Industrial Exhibition Halls.
63
49
29
62
45
35
19
87
Operating Voltage (Un)
Operating Frequency
Rated Current (In)
Current Range (   I)
Accuracy
Power Consumption
Display
Data retention duration
Pulse LED
Communication interface
Communication baudrate
Parity
ModBus Adress
Operating Temperature
Storage Temperature
Box Protection Class
Cable Section
EMC / Pollution Stability
Surge Voltage Test
Test
EFT
Installation
Weight
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
Please look at labels on the device.
50/60 Hz.
5 A (maximum 32A)
0.02-32A
Class B (EN-50470-1)
< 2 VA
6+1 digit = 999999,9 kWh
> 40 year
When the current is more than 0.02A it blinks proportional to the consumed energy.
RS-485 ModBus RTU
1200, 2400, 4800, 9600, 19200, 38400
No, Odd, Even
1-247
-
°C .... + 5 °C
25
5
IP51
4 mm²
4 kV 1.2 / 50 µs. (IEC 1000-4-5)
4 kV (IEC 1000-4-4)
Standart DIN mount (DIN EN60715)
60 gr. (excluding the packet)
`
At first start, device displays the screen located below for 1 second. Here;
Show ModBus register adress between 001-247
First 3 digits     :
s
Shows communication baudrate as 0=1200, 1=2400,2=4800, 3=9600,4=19200, 5=38400
5th digit     :
Shows parity type as 0 = No, 1 = Odd, 2 = Even Parity type. These parameters can be also
7th digit :
read and written at the ModBus registers address.
This device has RS-485  communication infstructure for remote monitoring.
Communication
Cautions
1. Connect the ES-32LS's terminals as shown in connection diagram.
ES-32LS does not require any periodical maintenance.
2.
Installing, repairing and operation should be performed by authorized person.
3.
Do not open the device. It does not include any parts that can be handled  by users.
4.
Do not use the device out of its purpose.
5.
Before operating your device, make sure that all connections are made properly.
6.
Please contact your dealer for any type of service required.
7.
Entes A.Ş. will not be responsible,
8.
if your device fails because of improper installation.
if your device fails because of natural disasters (fire, lighting, etc.).
if your device fails because of liquid penetration into the device or contact to any liquid for any
reason.
if the device or its software is interfered for any purposes.
if the serial number on the device is damaged.
if the device is out of order because of improper and careless use.
if the device is out of order defected during transportation out of Entes's responsibility.
ENGLISH
Applications
ENTES Elektronik Cihazlar Imalat ve Ticaret A.S.
Adress : Y. Dudullu OSB;  1. Cadde; No: 23
34775 Umraniye - ISTANBUL / TURKEY
Tel    : 0 216 313 01 10
Fax   : 0 216 314 16 15
www.entes.com.tr
ES-32LS 230V 5(32)
A
S
Index values are shown with this formula
Index = 65536 x register[4] + register[5]
Frequency (100xHz)
Power Factor
(1000x)
Active Power
(100xkW)
Reactive Power
(100xkVAr)
Apparent Power
(100xkVA)
*
The last two digits of the device serial number is used as modbus address
factory default value. If the last two digits are “00”, 100 is used for device’s
Modbus address. All devices in the package are placed in order.
R
R
R
R
R
8
9
10
11
12
0-65535
0-65535
0-65535
0-65535
0-65535
-
-
-
-
-
-     °C .... +     °C
40
70
Note: Should not be used for billing purposes.