Product information for LOGO! manual
A5E00167931-01
Options of connecting a Pt100 thermocouple
You can connect a Pt100 thermocouple to the module in
2- or 3-wire technique.
When you select the 2-wire technique, you must jum-
per terminals M1+ and IC1 or M2+ and IC2. Measure-
ment errors due to measurement cable resistance will
not be compensated with this type of connection.1
W
cable resistance is proportional to a measurement error
of  +2.5
Ă°
C.
With 3-wire connection, the influence of the cable
length (resistance) on the measurement result will be
suppressed.
M1+
PE
L+ M
RUN/STOP
L+ M
IC1
IC2
M1- M2+
M2–
Pt100
M1+
PE
L+ M
RUN/STOP
L+ M
IC1
IC2
M1- M2+
M2–
Pt100
2
-
wire technique
3
-
wire technique