Siemens 6ED1055-1FB00-0BA1 - 6ED1055-1FB00-0BA1 数据表

产品代码
6ED1055-1FB00-0BA1
下载
页码 346
17
Product information LOGO!
A5E00324307-01
2.3
Expansion modules
The following expansion modules can be connected to the LOGO!:
Symbol
Name
Power supply
Inputs
Outputs
LOGO! DM 8 12/24R
12/24 V DC
4 digital
4 relays (5A)
LOGO! DM 8 24
24 V DC
4 digital
4 solid state
24V / 0.3A
LOGO! DM 8 24R 
(3)
24 V AC/DC
4 digital
4 relays (5A)
LOGO! DM 8 230R
115...240 V AC/DC
4 digital 
(1)
4 relays (5A)
LOGO! DM 16 24
24 V DC
8 digital
8 solid state
24V / 0.3A
LOGO! DM 16 24R
24 V DC
8 digital
8 relays (5A)
LOGO! DM 16 230R
115...240 V AC/DC
8 digital 
(4)
8 relays (5A)
LOGO! AM 2
12/24 V DC
2 analog
0 ... 10V or 0
... 20mA 
(2)
none
LOGO! AM 2 PT100
12/24 V DC
2 Pt100
–50 
°
C to
+200 
°
C
none
(1): Different phases are not allowed within the inputs.
(2): 0 ... 10 V, 0 ... 20 mA can be connected optionally.
(3): Digital inputs can be operated either with P or with N action.
(4): Two groups consisting of 4 inputs each. Each group must be connected to
the same phase. It is possible to interconnect groups with a different phase.
2.4
Setup with different voltage classes
Rules
Digital modules can only be connected to devices of the same voltage class.
You may connect analog and communications modules to devices of any voltage
class.
You may replace two similar DM8 expansion modules by one appropriate DM16 ex-
pansion module (and vice versa) without having to change the circuit program.
Note
Two DM8 12/24R may be replaced by one DM16 24R only if operated with a power
supply of 24 V DC.
Two DM8 24R may be replaced by one DM16 24R only if operated with DC and
P action.