5.1 Constants and connectors
LOGO!Soft Comfort Online Help
Operating Instructions, 06/2014
Operating Instructions, 06/2014
197
Some of the input terminals of the LOGO! 0BA6 versions 12/24RC, 12/24RCo, 24/24o, 24C
and 24Co have a dual definition: they can be used as either digital inputs or analog inputs.
See the
LOGO! Manual
or product information for specific information about specific
modules. Circuit programs written for these modules for the LOGO! 0BA5 release and earlier
can run on LOGO! 0BA6 modules without modification. New circuit programs can make use
of the new input features, which provide additional fast-speed counters and analog
capability.
For help on analog block parameters, refer to information on analog value processing
For help on analog block parameters, refer to information on analog value processing
(Page 286).
The block input number is not determined by the hardware structure in
systems operating with devices of the 0BA0 to 0BA2 series.
This block is not available in the UDF Editor.
5.1.1.10
Analog outputs
Eight analog outputs are available, namely AQ1, AQ2, ... AQ8. You can only set an analog
value at the analog output, that is, a function with an analog output or analog flag AM.
If you connect a special function (that has an analog output) to a real analog output, then
If you connect a special function (that has an analog output) to a real analog output, then
note that the analog output can only process values from 0 to 1000.
You can configure the behavior of analog outputs for LOGO! 0BA5 and higher versions in
You can configure the behavior of analog outputs for LOGO! 0BA5 and higher versions in
STOP mode. Analog outputs can retain their last values when LOGO! goes to STOP mode.
Alternatively, you can configure specific values to be set for AQ1 and AQ2 (AQ1 and AQ8 for
0BA8) when LOGO! goes to STOP mode.
You can also set the analog output value range. You have two choices:
● Normal (0 V to 10 V or 0 mA to 20 mA)
● 4 mA to 20 mA
You can also set the analog output value range. You have two choices:
● Normal (0 V to 10 V or 0 mA to 20 mA)
● 4 mA to 20 mA
0BA0 to 0BA5: You cannot configure the behavior of AQ1 and AQ2 on
transition to STOP mode for LOGO! modules prior to the 0BA5 device series.
This block is not available in the UDF Editor.