Reference material 
 
5.3 Special functions 
LOGO!Soft Comfort Online Help 
Operating Instructions, 06/2014 
241
 
 
Example 8: Monthly selected, On Time = 2008.**.01, Off Time = 2010.**.05. Starting in 2008, 
on the first day of each month the timer output switches on and switches off on the fifth day 
of the month. The timer continues in this pattern through the last month of 2010. 
 
Description of the function 
The yearly timer sets and resets the output at specific on and off dates. Sets and resets are 
executed at 00:00. If your application requires a different time, use a weekly timer together 
with a yearly timer in your circuit program. 
The On Time specifies the month and day when the timer is set. The Off Time identifies the 
month and day on which the output is reset again. For the on and off times, note the order of 
the fields: The first field defines the year, the second the month and the third the day.  
When you select the Monthly check box, the timer output switches on each month at the 
specified day of the start time and remains on until the specified day of the Off Time. The On 
Year specifies the initial year in which the timer is activated. The Off Year defines the last 
year in which the timer turns off. The maximum year is 2099. 
If you select the Yearly check box, the timer output switches on each year at the specified 
month and day of the start time and remains on until the specified month and day of the Off 
Time. The On Year specifies the initial year in which the timer is activated. The Off Year 
defines the last year in which the timer turns off. The maximum year is 2099.  
If you select the Pulse Output check box, the timer output switches on at the specified On 
Time for one cycle and then the timer output is reset. You can choose to pulse a timer on a 
monthly or yearly basis, or just a single time. 
If you select none of the Monthly, Yearly, or Pulse check boxes, you can define a specific 
time period with the On Time and Off Time. It can span any time period that you choose. 
For a process action that is to be switched on and off at multiple but irregular times during 
the year, you can define multiple yearly timers with the outputs connected by an OR function 
block. 
 
 
The Yearly and Pulse Output settings are available only as of the 0BA6 device 
series 
The Monthly setting is available only as of the 0BA4 device series.