4.4 Special functions list - SF
LOGO!
Manual, 06/2014, A5E33039675
Manual, 06/2014, A5E33039675
163
Symbol in LOGO!
Wiring
Description
Cam parameter
At the Cam parameter, you configure the timer mode,
the on-/off-times for the timer, and whether the output
is a pulse output.
Output Q
LOGO! sets Q when the configured cam is on.
Timing diagrams
Example 1: Yearly mode on, Monthly mode off, Pulse Off, On Time = 2000-06-01, Off Time =
2099-08-31: every year on June 1 the timer output switches on and remains on until August
31.
Example 2: Yearly mode on, Monthly mode off, Pulse on, On Time = 2000-03-15, Off Time =
2099-**-**: every year on March 15, the timer switches on for one cycle.
Example 3: Yearly mode on, Monthly mode off, Pulse off, On Time = 2008-06-01, Off Time =
2010-08-31: on June 1 of 2008, 2009, and 2010 the timer output switches on and remains on
until August 31.