LOGO! functions 
 
4.4 Special functions list - SF 
 
LOGO! 
208
 
Manual, 06/2014, A5E33039675 
Bar graphs can be either horizontal or vertical representations of the current or actual value 
scaled between the minimum and maximum value. For more information on configuring and 
displaying bar graphs in message texts, refer to the Online Help for LOGO!Soft Comfort. 
Editing message texts 
You can only edit simple message texts from LOGO! Basic. You cannot edit message texts 
that contain features such as bar graphs, I/O status names, and others from LOGO! Basic. 
You can only edit these types of message texts from LOGO!Soft Comfort. 
Also, you cannot edit message texts from LOGO! Basic that contain any of the following 
parameters: 
●  Par 
●  Time 
●  Date 
●  EnTime 
●  EnDate 
●  Analog input 
●  Digital I/O status 
●  Special characters (for example: ±, €) 
You can only edit such message texts from LOGO!Soft Comfort. 
Changing parameters in the active message text 
When the message text is active, press ESC to select the editing mode. 
 
 
Note 
You must keep the ESC key pressed for at least one second. 
 
Press   and   to select the relevant parameter. Press OK to change the parameter. Use the 
 and   keys to edit a parameter. 
Confirm your changes with OK. You can now edit further parameters in the message text (if 
any exist). Press ESC to exit editing mode. 
Key input simulation in the active message text 
You can enable the four cursor keys C  , C  , C   and C   in an active message text by 
pressing ESC plus the relevant cursor key.