Application 
 
ÖLFLEX
®
 550 P cables are high flexible oil-resistant power cables with an isolation of a compound of rubber and an outer 
sheath of Polyurethane for flexible use and fixed installation for increased mechanical abuse. They are for use in dry, damp 
and wet rooms. Under following to the indicate temperature range is a use outside possible. Continuous, busy movements, 
usage  of  these  cables  in  moving  cable  carriers,  respectively  on  motor  drum  guidance  or  under  a  strain  of  more  than  15 
N/mm²  is  not  allowed.  ÖLFLEX
®
  550  P  cables  are  increased  oil  resistant  and  at  room  temperature  generally  resistant 
against acids and caustics solution. The outer sheath is resistant against high mechanical abuse, particularly to abrasion and 
grinding abuse. ÖLFLEX
®
 550 P cables are resistant against cuts, microbe proof and hydrolysis resistant. 
Application range: 
as power cable for construction machinery, stage applications as well as for portable handheld electrical devices  
 
 
Design 
 
Approvals
 
 
< 1.0 mm
2
: H05BQ-F 
 
 
acc. to EN 50525-2-21 resp. VDE 0285-525-2-21 / VDE 0282-10 resp. HD22.10 S2 
 
 
 
≥ 1.5 mm
2
: H07BQ-F 
 
 
acc. to EN 50525-2-21 resp. VDE 0285-525-2-21 / VDE 0282-10 resp. HD22.10 S2 
 
Conductor 
 
bare copper, fine wire strand in accordance to IEC 60228 resp. VDE 0295, class 5 
 
Core insulation 
rubber compound EI 6 acc. to EN 50363-1 resp. VDE 0207-363-1 
 
Core identification 
 
acc. to VDE 0293-1, with or without GN/YE ground conductor 
 
 
up to 5 cored coloured acc. to HD 308 S2 that is VDE 0293-308 
 
Outer sheath 
Polyurethane compound TMPU, acc. to EN 50363-10-2 resp. VDE 0207-363-10-2 
 
Colour: orange, similar to RAL 2003 
 
 
 
Electrical properties 
 
Nominal voltage 
 
< 1,0 mm
2
 
U
0
/U:  300 / 500 V 
 
 
≥ 1,5 mm
U
0
/U:  450 / 750 V 
 
Test voltage 
Core / Core: 
 3000 V AC 
 
 
Mechanical and thermal properties 
 
Min. bending radius 
for flexible use:     
12,5 x outer diameter 
 
fixed installation:    
     4 x outer diameter 
 
Temperature range 
occasional flexing:   
-40 °C up to +90 °C  
 
fixed installation:  
-40 °C up to +90 °C  
 
Oil resistance 
acc. to EN 50363-10-2 resp. VDE 0207-363-10-2 
 
Tests                                 
acc. to IEC 60811, EN 50395, EN 50396 
 
EC-Directives 
This cable is conform to the EC-Directives 2006/95/EC (Low Voltage Directive)  
 
and 2011/65/EU (RoHS, Restriction of the use of certain hazardous substances).