Fanox 12165 PF16-R Pump Protection Relay 12165 数据表

产品代码
12165
下载
页码 2
16
•  Eliminates need for level sensors to detect dry 
running.
•  For 3-phase motors from 1 to 630 A and over. 
Cable feed through relay itself.
•  Precise motor heating and cooling memory, 
reproduces its thermal image.
• Visual indication of tripping cause.
• Adjustable reset time for cos 
 .
Suitable for 3-phase submersible pumps, petrol 
station pumps, and other type of pumps and 
systems where running without load is critical (dry 
well, broken transmission belt, etc.).
The great advantage of these relays is that, by 
using the motor itself as a sensor and without 
requiring any external detectors, they monitor the 
cos 
  of the motor and stop it before a breakdown 
caused by dry running, cavitation or closed valve 
occurs.
MODELS
PF 16-R
PF 47-R
Adjustment range
 Motor  400 V
50/60 Hz
I
B
 (A)
4 - 16,6
16 - 47,5
CV
2 - 10
10 - 30
kW
1,5 - 7,5
7,5 - 22
Code
  
according to the 
relay voltage supply 
(+15% -10%) 
ac: 50/60 Hz
400/440 Vac
3-phase 
(motor)
12165
12167
230 Vac
3-phase 
(motor)
12173
12168
For 
,
N
 
of the motor below the minimum setting 
,
B
Pass the cables several times (n) through the holes in the relay
 
,
B
 = n x 
,
N
For 
,
N
 
of the motor above the maximum setting 
,
B
Use 3 CT .../5 and the relay P 19
External display module (optional)
ODPF
CHARACTERISTICS
Thermal memory / Overload trip
Yes / From 1,1 x 
,
B
Maximum motor nominal voltage
440 Vac
Trip classes (IEC 947-4-1)
10 - 20 - 30
Phase sequence protection
Yes
Phase imbalance protection
Over 40%. Tripping time < 3s
Underload protection by cos 
 / Trip delay
cos 
  adjustable from 0,15 to 1,0 / adjustable from 5 to 45s
Reset mode for protection against dry running
cos 
  automatic (adjustable) and remote. More info in page 28
Reset mode for other protection functions
   
 Manual, remote and automatic. More info in page 28
Signalling LED’s
4 LED’s: ON + 
  + 
cos   +   
Output contacts
1 relay with 1 NO + 1 NC
Switching power 
I
th
: 5A; AC15 - 250V - 2A; DC13 - 30V - 2A
Terminals: Max. section / screw torque
2,5 mm
2
, No. 22 - 12AWG / 20Ncm, 1.8 LB - IN
Power consumption
1,5W - 12 VA (230 Vac) - 20 VA (400 Vac)
Protection degree / weight / mounting
IP20 / 0,5 kg / DIN rail 
Storage temperature
-30°C +70°C
Operation temperature / max. altitude
-15°C +60°C / 1000m; -15°C +50°C / 3000m
Standards
IEC 255, IEC 947, IEC 801, EN 50081-2
   
THREE PHASE PUMP PROTECTION
DIMENSIONS PS RELAY (mm)
Settings and curves,see pages 24 to 29.
WIRING DIAGRAM (mm)
PF
PROTECTION
FUNCTIONS
  Overload
cos   Underload
  Phase imbalance 
or phase loss
Phase sequence
80
35,4
38
45
99
94
5
78
Ø10
12
14
56,5
33
PF 47--R
PF 16-R
80
35,4
38
45
99
94
5
78
17,5
12*
12
17,5
50
Underload protection by cos  
Pump protection relays
 
(Without level sensors)
L3
L2
L1
13
14
A2
N
K1
A1
L1
13-K1
14-K1
98
96
95
L1
U1 V1 W1
L2
L3
97
Tripped
or Us=0
Normal
98
98
97
97
96
96
95
95
M
3
PF
PF
www.fanox.com
fanox@fanox.com
Tlf. +34 94 471 14 09
Fax +34 94 471 05 92
10/2010/D00