Fanox 12012 ST4 Phase And Thermistor Relay 12012 数据表
产品代码
12012
33
DIMENSIONS ST RELAY (mm)
WIRING DIAGRAM (mm)
ST
ST-D
Phase imbalance
or phase loss
Phase sequence
Overtemperature
Phase sequence
Overtemperature
MODELS
ST2
ST4
ST2-D
ST4-D
Nominal voltage of the line to
be monitored (±15%)
be monitored (±15%)
3 x 230 V
3 x 400 V
3 x 230 V
3 x 400 V
Voltage supply (±15%)
Self-powered (3-phase)
Code
12001
12012
12002
12013
CHARACTERISTICS
Nominal frequency
50/60 Hz
Control range
Phase loss: with resistive loads it trips when a phase loss occurs.
With three-phase motors it trips if the voltage regenerated by the
motor is lower than 60% of the main voltage. Phase imbalance >
40%
With three-phase motors it trips if the voltage regenerated by the
motor is lower than 60% of the main voltage. Phase imbalance >
40%
PTC sensor: min/max cold resist
- Trip resist
- Trip resist
100Ω / 1500Ω - 2300Ω
Trip time delay
< 0,1 s
Reset mode
Automatic
Signalling LED’s
3 LED’s: ON +
+
Output contacts
1 relay with 1 change over NO - NC
2 relays (
+
) with 1 NO
Switching power
I
th
: 5A; AC15 - 250V - 2A; DC13 - 30V - 2A
Maximum terminal section /
screw torque
screw torque
2,5 mm
2
, No. 22 - 12AWG / 20Ncm, 1.8 LB - IN
Power consumption
7,5 VA (230 Vac) - 11 VA (400 Vac)
Protection degree / weight
IP20 / 0,12 kg
IP20 / 0,13 kg
Storage / operation
temperature
temperature
-30°C +70°C / -15°C +60°C
22,5
72,6
100
22,4
61,5
80
WORK LOGIC
Tripped
or Us=0
or Us=0
Normal
RST
RST
RST
RS
T
RTS
RELAY
PTC
RELAYS
11-14
21-24
PTC
Tripped
or Us=0
or Us=0
Normal
ST-D
ST
ST
• Self-powered by the voltage to be monitored.
• Visual indication of trip cause.
• DIN rail mounting.
• To protect 3-phase devices
• Suitable for motors with built-in PTC sensors in applications
such as elevators, cranes, hoists and similar installations.
• Sensitive to incorrect phase sequence.
• Monitoring of short circuit and broken wire in PTC circuit.
ST-D model:
Two output relays, one for phase imbalance, phase loss and
phase sequence and the other for over temperature.
Two output relays, one for phase imbalance, phase loss and
phase sequence and the other for over temperature.
PHASE AND TEMPERATURE CONTROL
ST-D
Tripped
or V=0
or V=0
14 11 12
14 11 12
Normal
T-L3
S-L2
R-L1
S-L2
R-L1
K1
A1
A2
N
M
3
T-L3
S-L2
R-L1
S-L2
R-L1
K1
M
3
PHASE and TEMPERATURE relays
CONTROL & MEASUREMENT
PROTECTION
FUNCTIONS
www.fanox.com
fanox@fanox.com
Tlf. +34 94 471 14 09
Fax +34 94 471 05 92