Tele 2330900A ONF3 Mains Disconnector Relay ONF3 DPDT-CO 2330900A 数据表

产品代码
2330900A
下载
页码 2
Subject to alterations and errors
Release 08/05
Monitoring relays - OCTO series
Mains decoupler with all-pole disconnectin
2 change-over contacts
Width 35mm
Installation design
Technical data
1. Functions
 0 
Automatic 
OFF
 I 
Automatic 
ON
2. Time ranges
  
Adjustment 
range
Tripping delay: 
fixed, approx. 6s
Rise time: 
fixed, approx. 0.5s
3. Indicators
Green LED ON: 
indication of supply voltage
Yellow LED ON: 
indication of relay output
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position: 
any
Shockproof terminal connection according to VBG 4 (PZ1 required), 
IP rating IP20
Tightening torque: 
max. 1Nm
Terminal capacity:
 
1 x 0.5 to 2.5mm² with/without multicore cable end
 
1 x 4mm² without multicore cable end
 
2 x 0.5 to 1.5mm² with/without multicore cable ends
 
2 x 2.5mm² flexibel without multicore cable ends
5. Input circuit
Supply voltage:
 230V 
AC 
terminals 
L
-N
 (bottom of device)
Tolerance: 
-15% to +10%
Rated frequency: 
48 to 63Hz
Rated consumption: 
11VA (1.6W)
Duration of operation: 
100%
Reset time: 
-
Residual ripple for DC:  -
Drop-out voltage: 
>10% of the supply voltage
6. Output circuit
2 potential free n.o. contacts  terminals L
 L
 - N
 N
 
(top of device)
Switching capacity: 
4000VA (16A / 250V AC)
Fusing: 
16A fast acting
Mechanical life: 
30 x 10
6
 operations
Electrical life: 
2 x 10
5
 operations
 
at 1000VA resistive load
Switching frequency: 
max. 60/min at 100VA resistive load
 
max. 6/min at 1000VA resistive load
 
(according to IEC 947-5-1)
Rated voltage: 
250V AC (according to IEC 664-1)
Rated surge voltage: 
4kV, overvoltage category  III
 
(according to IEC 664-1)
7. Measuring circuit
Measuring circuit: 
terminals see output circuit
Measuring voltage: 
200 to 250mV DC
Activation current I
ON
5 to 200mA
Release current: 
fixed, approx. 70% I
ON
8. Accuracy
Base accuracy: 
±10% (of maximum scale value)
Adjustment accuracy: 
≤5% (of maximum scale value)
Repetition accuracy: 
≤2%
Voltage influence: 
≤0.5% / V
Temperature influence: 
≤0.1% / °C
9. Ambient conditions
Ambient temperature: 
-25 to +55°C (according to IEC 68-1)
Storage temperature: 
-25 to +70°C
Transport temperature: 
-25 to +70°C
Relative humidity: 
15% to 85%
 
(according to IEC 721-3-3 class 3K3)
Pollution degree: 
2, if built-in 3
 
(according to IEC 664-1)
ONF3
1.03-13