Instruction Manual
GB
Time switch
müller SC 18.10 pro / SC 28.X0 pro / SC 28.X1 pro     paladin 170 410 pro / 172 4X0 pro / 172 4X1 pro
Connection diagram 
Directory 
1. Safety instructions 
2. Initial operation 
1 channel
 
SC 28.10 pro / 172 410 pro
SC 28.11 pro / 172 411 pro
SC 18.10 pro / 170 410 pro
2 channel
SC 28.20 pro / SC 28.21 pro / SC 172 420 pro / 172 421 pro
1. Safety instructions 
2. Initial operation 
3. Menu overview 
4. Symbol legend 
5. Key function 
6. Handling advice 
7. Channel ON  OFF / Permanent P 
8. New Program 
9. Example „New Program“ 
10. Pulse 
11. Program permanent 
12. Additional adjustments 
13. Program modify 
14. Data-key
*
!
The installation and assembly of electrical equipment 
must be only carried out only by a skilled Person! 
Otherwise fire danger or danger of an electric shock 
exists! 
!
Connect the supply voltage/frequency as stated on the 
product label! 
!
Warranty void if housing opened by unauthorised 
person!
!
The electronic circuit is protected against a wide range 
of external influences. Incorrect operating may occur if 
external influences exceed certain limits!
ƒ
The time switch is delivered in sleep-mode, the display is switched off. 
ƒ
Press 
-button for 1 second. 
ƒ
The current date and time is already programmed and European daylight 
savings time is activated. 
ƒ
Select the desired language by pressing 
-buttons and confirm it by 
pressing 
(Remark: By pressing 
 you move one step backwards from 
the current position)
ƒ
If required, date, time and daylight savings time mode can be adjusted also 
by pressing 
-buttons and a subsequent confirmation with 
.
3. Menu overview 
4. Symbol legend 
Channel is switched ON 
Channel is switched OFF 
For the current date the “holiday program” / “permanent by date” is activated 
Standard programming step 
Current state is based on a manual over-ride. The state will be cancelled with the next programming step. 
Current state is based on a manual over-ride. The state is permanent until terminated manually (7). 
Days of the week Monday, Tuesday, ... Sunday;  
The underscores indicate if the program is active for the days above. 
Element within sub-menu “program delete” 
The time switch is locked; to unlock the device the PIN has to be entered (12). 
5. Key function 
6. Handling advice 
7. Channel ON OFF / Permanent P 
1. To access the Enter-mode (program, adjustments, options) from the automatic-mode. 
2. To revert to the beginning of the current (sub-) menu.   
1. To adjust the flashing digit. 
2. To scroll through a choice 
1. Automatic-mode: To switch the channel ON or OFF until the next programming step occurs. 
2. Automatic-mode: A push longer than 3 sec. = Permanent switching status (7). 
1. To activate the time switch when operated without power supply. 
2. To confirm the selection or the entered data. 
ƒ
The time switch is programmable without external power supply after 
pressing the   -button. 
ƒ
To revert one step or one level back while in the Enter-Mode press 
.
ƒ
After completion of a (sub-) menu confirming 
end
 will return the device 
into the automatic-mode. 
ƒ
With 
 the choice changes from 
end
 to 
continue
. By confirming 
continue
 the time switch returns to the beginning of the current  
(sub-) menu. 
ƒ
When confirming 
end
 before completion, the time switch returns to the 
automatic-mode without saving the entered data. 
Channel 
ON OFF
By pushing 
-buttons (
-buttons) a manual switch of the 
channels take place. The resulting switching status is marked 
with the hand-symbol and remains until the next programming 
step occurs. (temporary over-ride) 
Permanent switching status P
By pressing the corresponding channel button 
for more 
than 3 sec. the channel is permanently switched ON or OFF. 
The status remains until the next manual switching occurs (> 3 
sec.). (permanent over-ride) 
8. New Program (See also the example (9)) 
9.  Example „New Program“ (For a regular switching time) 
Step A. to C. please refer to point 9. (Example “New Program”)
A. If power supply is disconnected press
 for one second. The display appears in Automatic-Mode. 
B. Press 
, the time switch is now in the Enter-Mode. 
C. Confirm 
Program
 with  .
D. Confirm 
new program
with
.
E. Choose the desired channel with 
 and confirm with  .
F. For regular switching times choose 
on
 or 
off
 with 
-buttons and confirm with  .
G. Within this level you activate the days of the week (1…7) on which the switching time should happen. 
With 
 you activate “yes” or deactivate “no” the corresponding date. Confirm each day with 
.
H. Adjustment of the time: Hours 
 and
. Minutes 
 and
.
I. Verify the entered switching time: If the flashing summary of the programming step is correct, verify 
on
 or
off with 
. After verification you have the choice between 
edit/delete
 and 
end
 with 
.
J. If you want to proceed with programming, confirm 
next switching
with 
.
To leave the programming menu confirm 
end
.
10. Pulse 
11. Program permanent 
Program
 -> New program -> Channel A/B -> …
The pulse function provides you the opportunity of programming a switching time with a defined duration. 
As soon as the pulse-duration has expired the time switch switches OFF automatically (the duration of the pulse is up to 59:59 mm:ss).  
The programming is carried out like a standard switching time (see point 8 / 9) with following differences 
ƒ
Choose 
Pulse
 function (9F). 
ƒ
Define the duration of the pulse (
pulstime minute
 / 
pulstime second
). 
ƒ
Program the days of the week 
ƒ
Program the switching time (
time hour
 / 
time minute
)
Validation: Confirm the blinking summary of the pulse program 
Program
 -> new program -> channel A/B -> permanent -> 
ƒ
One permanent by date programming step (holiday function) for each channel is possible. During the 
desired period (The function is valid for the whole days) the channel can be switched off (
permanent 
off
) or on (
permanent on
). 
ƒ
The programming of this function is as described in (8 / 9). 
ƒ
The choice 
permanent
 will not be offered anymore within the menu 
new program
 when already in 
use. The switching time can be modified and deleted within 
Program modify
 (13) and 
Program 
delete
 (12) respectively. 
12. Additional adjustments 
13. Program modify 
Menu
Main menu
Application
Program query 
Program 
To query the programming steps and remaining memory locations
Program copy 
Program 
Copy from one channel to another. Memory of the channel won’t 
be overwritten; the copied switching steps appear additionally. 
!
Permanent by date function is not copied! 
Program delete 
Program 
Deletion of switching time(s). The program for all channels, single
channels and single programming steps within on channel can be 
deleted. 
Date-Time 
Adjustment 
Adjustment of date and time 
Summertime 
Adjustment 
Adjustment of the daylight saving time mode (ON/OFF) 
Language  
Adjustment 
Choice of languages 
Program
 -> Program modify -> …
Within 
Program modify
 each single switching time can be modified. 
Factory Defaults
*
Adjustment 
Reset to the state of delivery. 
!
Date, time and switching program will be lost! 
14. Data-key
*
Counter 
Options 
Displays the hour counter and pulse counter for each channel and
the time switch itself. 
PIN-Code 
Options 
The time switch can be locked with a 4-digit PIN-Code. The code 
can be adjusted, activated and deactivated. If you have forgotten 
the Code please call customer service. 
Reset-Function
Press all front keys for 2 seconds. The time switch is reset. The values for date 
and time will be deleted and have to be re-entered. The switching program has 
not been deleted! 
With a Data-key following activities are possible: 
ƒ
Save data
: Writes the data from the time switch into the memory of the Data-key. 
ƒ
Program timeswitch
: Writes the data located inside the Key into the memory. 
ƒ
Key function
: The time switch will solely apply programming steps from the Data-
key. The switching program of the time switch is suppressed. 
ƒ
Key readout
: To query the switching program of the Data-key.