Finder 58.34.9.125.5050 Relay 58.34.9.125.5050 数据表

产品代码
58.34.9.125.5050
下载
页码 6
4
Contact specification
Nominal
Coil
Operating range
Resistance Rated coil
voltage
code
absorption
U
N
U
min
U
max
R
at U
N
(50Hz)
V
V
V
Ω
mA
12
8.012
9.6
13.2
50
97
24
8.024
19.2
26.4
190
53
48
8.048
38.4
52.8
770
25
110
8.110
88
121
4,000
12.5
120
8.120
96
132
4,700
12
230
8.230
184
253
17,000
6
Nominal
Coil
Operating range
Resistance Rated coil
voltage
code
absorption
U
N
U
min
U
max
R
at U
N
V
V
V
Ω
mA
12
9.012
9.6
13.2
140
86
24
9.024
19.2
26.4
600
40
48
9.048
38.4
52.8
2,400
20
125
9.125
100
138
17,300
7.2
AC coil data
DC coil data
Coil specifications
F 58 - Electrical life (AC) v contact current
2 & 3 pole relays
H 58 - Maximum DC1 breaking capacity
• When switching a resistive load (DC1) having voltage and current   
values under the curve, an electrical life of ≥ 100·10
3
can be expected.
• In the case of DC13 loads, the connection of a diode in parallel with
the load will permit a similar electrical life as for a DC1 load.
Note: the release time for the load will be increased.
- Max. permitted coil voltage.
- Min. pick-up voltage with coil at ambient temperature.
R 58 - DC coil operating range v ambient temperature
R 58 - AC coil operating range v ambient temperature
- Max. permitted coil voltage.
- Min. pick-up voltage with coil at ambient temperature.
F 58 - Electrical life (AC) v contact current
4 pole relay
Cycles
Resistive load - cos
ϕ = 1
Inductive load - cos
ϕ = 0.4
Cycles
Resistive load - cos
ϕ = 1
Inductive load - cos
ϕ = 0.4
DC voltage (V)
DC breaking current (A)
contacts in series
2 & 3 pole current limit
4 pole current limit
4
3
2
1
1
2
1
2
II-2014, www
.finder
net.com
58
SERIE S
58 Series - Relay interface modules 7 - 10 A
B