2. Safety regulations / Installation notes 
• When working on the device, observe the national 
safety rules and regulations for the prevention of 
accidents.
• Disregarding these safety regulations may result 
in death, serious personal injury or  damage to 
equipment.
• The device may only be started up, assembled, 
modified or retrofitted by an authorized 
electrician.
• Before working on the device, disconnect the 
power.
• In devices with 230 V AC activation, always use 
the same phase for the control supply voltage and 
the control inputs!
• For emergency stop applications, the machine 
must be prevented from restarting automatically 
by a higher-level control system.
• During operation, parts of electrical switching 
devices carry hazardous voltages.
• During operation, the protective covers must not 
be removed from the electric switchgear!
• Please retain the instructions.
• The device is an associated item and must not be 
installed in potentially explosive areas. Adhere to 
the relevant safety regulations when setting up 
and operating the relevant equipment.
• The safety regulations applicable when motors 
are used in the Ex area must be complied with 
(ATEX directive 94/9/EC).
• If the "Automatic RESET" operating mode is used, 
the drive is switched on after the cooling time has 
elapsed provided there is one more activation 
signal. The cooling time is 20 minutes. An 
automatic restart is not permissible in the case of 
applications in the Ex-protection area.
• The device may not be subjected to mechanical 
and thermal loads that exceed the thresholds 
specified in the operating manual. If required, the 
device should be installed in an appropriate 
housing with suitable protection (e.g. IP54) 
according to IEC 60529/EN 60529 to provide 
protection against mechanical and electrical 
damage. Where dusts are present, the device 
must be installed in a suitable housing (at least 
IP64) in acc. with EN 61241. 
• Installation should be carried out following the 
instructions given in this data sheet. The circuits 
inside the device must not be accessed during 
operation.
• The operating equipment cannot be repaired by 
the user and must be replaced by an equivalent 
device. Repairs may only be carried out by the 
manufacturer.
• The safety data and features provided according 
to the EC-type examination are listed after the 
technical data.
• The device carries out a diagnosis of the functions 
when the drive is being switched on or when it is 
switched off. In addition, an (electrically) skilled 
person or a skilled worker who is well acquainted 
with the relevant standards can conduct the 
"Motor overload protection" safety function test. 
For this test, the drive must be operated with 
forward or reverse running, thus interrupting the 
current flow in a conductor (e.g. by removing the 
fuse in the L1 or L3 phase). The hybrid motor 
starter then switches the drive off within a period 
of 1.5...2 s. The LEDs for forward or reverse 
running activation extinguish and the Err-LED and 
the reply output are set.
• If the connecting cable for remote reset is longer 
than 3 m in 230 V AC devices
 
(ELR H5-IES-230AC/...), it must be shielded.
• The device must be secured with the help of an 
access protection during safety-related 
applications.
• Only use power supply units with safe isolation 
and PELV in accordance with EN 50178/VDE 
0160 (PELV). This prevents short circuits be-
tween primary and secondary sides.
Scope of use: 
• In circuits in potentially dust-explosive areas of 
zones 21 and 22, it must be guaranteed that the 
equipment connected to this circuit complies with 
categories 2D or 3D or is certified as such.
• This is a product for environment A (industry). In 
environment B (household), this device can 
cause undesired radio interference; in such a 
case, the user may be under obligation to 
implement appropriate measures.