Easy to communicate between devices 
 
7.8 S7 communication 
Easy Book 
Manual, 03/2014, A5E02486774-AF 
155
 
7.8.3 
GET/PUT connection parameter assignment 
The GET/PUT instructions connection parameter assignment is a user aid for configuring S7 
CPU-CPU communication connections. 
After inserting a GET or PUT block, the GET/PUT instructions connection parameter 
assignment is started: 
 
The inspector window displays the properties of the connection whenever you have selected 
any part of the instruction. Specify the communication parameters in the "Configuration" tab 
of the "Properties" for the communication instruction.  
After inserting a GET or PUT block, the "Configuration" tab automatically appears and the 
"Connection parameters" page is immediately shown. This page allows the user to configure 
the necessary S7 connection and to configure the parameter "Connection ID" that is 
referenced by the block parameter "ID". A "Block parameters" page allows the user to 
configure additional block parameters. 
 
 
Note 
V4.0 CPU program GET/PUT operation is not automatically enabled 
A V3.0 CPU program GET/PUT operation is automatically enabled in a V4.0 CPU. 
However, a V4.0 CPU program GET/PUT operation in a V4.0 CPU is not automatically 
enabled. You must go the CPU "Device configuration", inspector window "Properties"tab, 
"Protection" property to enable GET/PUT access (Page 82).