Siemens 6AV6651-7KA01-3AA4 - S7-1200 + KTP400 Basic Starter Kit 6AV6651-7KA01-3AA4 用户手册

产品代码
6AV6651-7KA01-3AA4
下载
页码 364
Easy to create the device configuration 
 
5.5 Configuring the operation of the CPU and modules 
 
Easy Book 
78
 
Manual, 03/2014, A5E02486774-AF 
The CPU initializes these bytes on the transition from STOP mode to STARTUP mode. The 
bits of the clock memory change synchronously to the CPU clock throughout the STARTUP 
and RUN modes. 
 
 
CAUTION 
Risks with overwriting the system memory or clock memory bits 
Overwriting the system memory or clock memory bits can corrupt the data in these 
functions and cause your user program to operate incorrectly, which can cause damage to 
equipment and injury to personnel. 
Because both the clock memory and system memory are unreserved in M memory, 
instructions or communications can write to these locations and corrupt the data.  
Avoid writing data to these locations to ensure the proper operation of these functions, and 
always implement an emergency stop circuit for your process or machine. 
 
System memory configures a byte with bits that turn on (value = 1) for a specific event. 
 
Table 5- 2 
System memory  
Reserved  
Value 0  
Always off 
Value 0 
Always on 
Value 1 
Diagnostic status 
indicator 
 
1: Change 
 
0: No change 
First scan indicator 
 
1: First scan after 
startup 
 
0: Not first scan 
Clock memory configures a byte that cycles the individual bits on and off at fixed intervals. 
Each clock bit generates a square wave pulse on the corresponding M memory bit. These 
bits can be used as control bits, especially when combined with edge instructions, to trigger 
actions in the user code on a cyclic basis.