Startup Procedures 
Siemens Building Technologies, Inc. 
 
31 
Additional Parameter Settings 
NOTE: 
If Display Selection for r0000, parameter P0005 = 21 (actual frequency), then the BOP 
display alternately shows setpoint values and the actual value (0 Hz).  
Flying Start 
Parameter Description 
Action 
Setting/ 
Default 
P1200 
Flying Start
 
Starts SED2 into a spinning 
motor by rapidly changing the 
output frequency of the SED2 
until the actual motor speed is 
found. Then, the motor runs up 
to setpoint using the normal 
ramp time.  
0 = Flying start disabled.  
1 = Flying start is always active, 
start in direction of setpoint.  
2 = Flying start is active, if power 
on, fault, OFF2, start in direction 
of setpoint.  
3 = Flying start is active if fault, 
OFF2, start in direction of 
setpoint.  
4 = Flying start is always active, 
only in direction of setpoint.  
5 = Flying start is active if power 
on, fault, OFF2, only in direction 
of setpoint.  
6 = Flying start is active if fault, 
OFF2, only in direction of 
setpoint. 
1. Press   to enter the SED2 
parameter mode and to display 
r0000
.  
2. Press   to advance to 
parameter P1200.  
3. Press   to access the 
parameter values level. 
4. Press   to advance to 
desired setting.  
5. Press   to confirm and save 
the setting. 
Minimum = 0 
Default = 0 
Maximum = 6 
Suggested = 2 
NOTES: 
1.  Flying start is useful for motors with high inertia loads.  
2.  Settings 1 through 3 search in both directions. Settings 4 through 6 search only in the direction of the 
setpoint.  
3.  Flying start must be used in cases where the motor may still be turning (such as after a brief input 
power break) or can be driven by the load. Otherwise, overcurrent trips occur.  
4.  If the SED2 faults on F0002 (overvoltage) on a start command, flying start may have to be optimized by 
reducing the values in P1203 and P1202.