NATURAL GAS
Length of Pipe 
- Ft.
Pipe Capacity - BTU Per Hour Input Includes Fittings
1/2”
3/4”
1”
1 1/4”
20
92,000
190,000
350,000
625,000
40
63,000
130,000
245,000
445,000
60
50,000
105,000
195,000
365,000
PROPANE GAS
Length of Pipe 
- Ft.
Pipe Capacity - BTU Per Hour Input Includes Fittings
Copper Tubing 
(Outside Diameter)
Iron Pipe
5/8”
3/4”
1/2”
3/4”
20
131,000
216,000
189,000
393,000
40
90,000
145,000
129,000
267,000
60
72,000
121,000
103,000
217,000
• ANSI - American National Standards Institute, Inc.  
oversees creation and maintenance of voluntary        
consensus standards, including ANSI Z21.13/CSA 4.9: 
Gas-Fired Low Pressure Steam and Hot Water Boilers.
• ASTM - American Society for Testing and Materials. 
ASTM International is one of largest voluntary standards 
development organizations in world trusted source for 
technical standards for materials, products, systems, 
and services. Known for their high technical quality and 
market relevancy, ASTM International standards have 
important role in information infrastructure that guides 
design, manufacturing and trade in the global economy. 
• AUTHORITY HAVING JURISDICTION - Individual 
or organization adopting and enforcing codes, rules, 
and by-laws governing various concerns of community. 
Commonly referred to as "final authority" for any matters 
relating to LIFE SAFETY and BUILDING CONSTRUCTION 
within a community.
• Btu - Abbreviation for British Thermal Unit. Quantity of 
heat required to raise temperature of 1 pound of water 
1°F.
• BURNER - Device for final conveyance of gas or mixture 
of gas and air, to combustion zone.
• COMBUSTION - Rapid oxidation of fuel gases 
accompanied by production of heat or heat and light. 
Complete combustion of fuel is possible only in presence 
of adequate supply of oxygen.
• COMBUSTIBLE MATERIAL - Materials made of or 
surfaced with wood, compressed paper, plant fibers, 
or other materials capable of being ignited and 
burned. Such material shall be considered combustible 
even though flame-proofed, fire-retardant treated, or 
plastered.
• CONDENSATE - Liquid separated from flue gas due to 
reduction in temperature.
• DIRECT VENT BOILER - Boiler constructed and installed 
so all combustion air is derived directly from outdoors 
and all vent gases are discharged to outdoors.
• DRAFT - Pressure difference causes gases or air to flow 
through a chimney, vent, flue or appliance.
• FLA - Full load amps.
• FLUE  GASES -  Products of combustion plus excess air 
in appliance flues or heat exchanger.
• HIGH-VOLTAGE - Circuit involving potential of not 
more than 600 volts and having circuit characteristics in 
excess of those of low-voltage circuit.
• IGNITER -  Device utilizing electrical energy to ignite 
gas at main burner.
• LEAK CHECK - Operation performed on gas piping 
system to verify system does not leak.
• LOW WATER CUTOFF - Device constructed to 
automatically cut off fuel supply when surface of water in 
boiler falls to lowest safe water level. 
• LOW-VOLTAGE - Circuit involving potential of not more 
than 30 volts.
• METRIC GAS METERS
MBH
=
127,116 x       cu meters
               Seconds
For example: Gas Meter measures 0.1 cubic Meters in 100  
                    seconds
MBH
=
127,116 x 0.1
 = 127 MBH
100
• PRESSURE TEST - Operation performed to verify gas 
tight integrity of gas piping following its installation or       
modification.
• PURGE - To free gas conduit of air or gas, or mixture of 
gas and air. 
• PURGE TIME - Period of time intended to allow for 
dissipation of any unburned gas or residual products of 
combustion.
• GAS PIPE SIZES Table 14
15 - GLOSSARY