Illustrated parts catalog  6 
Life safety component identification 
 
 
Item 
Component 
Description 
Exit sign locations 
Indicates the location of an exit 
EPO strobe 
Red—An EPO event occurred and the HP POD 20c shut down. 
EPO button 
Enables manual initiation of the EPO system 
EPO alarm  
Indicates the initiation of the EPO system with an audible alarm 
Fire strobe light 
Indicates a fire alarm condition within the HP POD 20c 
Fire suppression alarm 
Indicates the initiation of the fire suppression system with an 
audible alarm 
Fire alarm manual pull* 
Enables manual initiation of the fire system, which includes 
activating the interior and exterior fire strobe lights and the 
optional fire suppression system 
Fire suppression abort button* 
Aborts the fire suppression system. A fire suppression abort 
button is located next to each personnel door. 
EPO button 
Disconnects the HP POD 20c from main power, activates the 
red EPO indicator on the control cabinet door, and activates 
the red EPO strobe on the HP POD 20c exterior. 
To restart the HP POD 20c after an EPO event, you must reset 
the EPO button by turning the key and switching the button to 
the Active position. 
 