Beck, R&J ELECTRIC ACTUATORS FOR INDUSTRIAL PROCESSCONTROL 11-1_9 用户手册

下载
页码 88
29
Split Range Operation
 
It is sometimes desirable or necessary to have 
more than one final control element controlling a 
single process.  Often, this type of control strategy 
requires that two to four Beck drives each respond 
to different portions of one 4–20 mA Demand signal 
from the control system.  
 
This type of operation is called split range 
operation.  For example, consider the most 
common split range scenario—two drives split 
ranged for 50% of the 4–20 mA Demand signal 
input.  Both drives are wired in parallel to receive 
the same 4-20 mA signal (note that the  250 Ohm 
R11
 
resistor (see DCM-2 illustration on page 
78) must be removed from one of the two drive 
DCM-2 boards to allow HART
®
 communications.  
If more than two drives are split ranged, the R11
 
resistor must be removed from all the DCM-2 
boards but one), but each drive’s interpretation 
of the signal must be different.  One drive must 
interpret 4–12 mA as 0–100% Demand, and 
one drive must interpret 12–20 mA as 0–100% 
Demand.  This requires that the drives have 
different Demand signal calibrations.
 
To set up a split range operation, follow the 
steps listed below (see page 24 for location of 
pushbutton controls).
NOTE:  Ensure that the L.O.S. (Loss of 
Demand input signal) settings of the drives are 
appropriate for the configuration.  See page 21 
for information on changing L.O.S. settings.
 1.  Remove the DCM-2 cover (1/2” bolt heads).
 2. Ensure the Handswitch is in the “STOP” 
position.  This will prevent the drive from 
repositioning during this procedure.
 3.  Apply the desired 0% Demand input signal to 
the drive.  (Following the example above, the 
minimum signal for the first drive would be 4 
mA.  The second drive’s minimum signal would 
be 12 mA).  If the drive has not been wired, the 
Demand input signal is connected at terminals 
AA (+) and BB (–) as shown in the diagram on 
page 17.
 4.  Press and hold the “CALIBRATE” pushbutton 
on the DCM-2 customer interface panel, then 
press the “SET DEM 0%” pushbutton  until the 
“ACKNOWLEDGE” LED is lit.*
 5.  Apply the desired 100% Demand input signal 
to the drive.  (Following the example above, 
the maximum signal for the first drive would be 
12 mA.  The second drive’s maximum signal 
would be 20 mA).
Demand
Square Function
Input
Actual Output
Signal
Standard Output
Position
(mA)
(% of Span)
(% of Span)
4.0
0
0
5.6
10
1
12.0
50
25
15.2
70
49
18.4
90
81
20.0
100
100
 6.  Press and hold the “CALIBRATE” pushbutton 
on the DCM-2 customer interface panel, then 
press the “SET DEM 100%” pushbutton until 
the “ACKNOWLEDGE” LED is lit.*
 7. Repeat this process for the remaining drives 
to be split-ranged.
 8.  Run the drive through its full operating range to 
ensure proper response to the Demand input 
signal.
 9.  Replace the DCM-2 cover.  Tighten the cover 
bolts to 10 lb-ft (14 N•m) torque.
* If the “ACKNOWLEDGE” LED does not light, but 
the “DEMAND” LED does light, the signal is out 
of acceptable range and was not accepted by 
the DCM-2.  This is typically caused by trying to 
set 0% and 100% values too close together (i.e., 
less than 4 mA difference).
Square Function
 
 Beck drives can be set up to position the output 
shaft proportionally to the square of the Demand 
input signal (see table below).  This function is 
factory configurable, or may be configured using 
the HART or Serial interface.