DCM-2 HART INTERFACE
 
Calibration
 
All Beck drives are shipped completely 
calibrated to the customer specifications, and 
are ready to be installed.  If the need arises to 
change the drive calibration, confirm that the 
drive is installed as specified and operating 
properly before proceeding with the change.  It 
is also helpful to verify the drive configuration.  
This can be done by reviewing the settings in the 
Configuration menu.
 
With the exception of the settings for the over-
travel limit switches, auxiliary limit switches and 
CPS, all calibration is performed using the HART 
interface and a communications tool (model 
275/375 HART
 
Communicator), as described in 
the Communications section of this manual.  If 
unfamiliar with the HART communicator and 
Beck drives, please review the Communications 
section of this manual before continuing.
 
The DCM-2 can be calibrated by using the 
"Position Setup" and "Demand Setup" menus.
 
Normally, calibration should not require 
adjustment; however, if the Position or Demand 
requires minor adjustment, the "Calibration Trim" 
menu may be used.     
 
Any calibration changes that are made 
using any of the above described methods, can 
be reversed by using the “Restore to Factory” 
feature in the "Configuration" menu.  Note that 
implementing the “Restore to Factory” feature 
returns all settings to the as-shipped factory 
settings.