POSITION SENSOR SETUP
 
In order to correctly position the drive output 
shaft in response to the input Demand signal, 
the DCM-2 board receives a position signal from 
the drive’s position sensor (CPS) and compares 
this actual position to the desired Demand input.  
This process requires that the DCM-2 interprets 
the CPS signal appropriately for the full range 
of desired travel.  The "PositionSensrSetup" 
submenu is used to set the DCM-2 to accept the 
CPS position signal and interpret the appropriate 
0–100% range.
 
All Beck drives are shipped completely set 
and calibrated to the customer specifications 
and are ready for installation.  Normally, no 
adjustments are necessary.
 
If, however, the position calibration needs to 
be changed, the "PositionSensrSetup" submenu 
must be used.  The "PositionSensrSetup" is 
accessible through the "Configuration" menu.
  
 
 
DCM-2 HART INTERFACE
 
Calibration - Position 
The "PositionSensrSetup" submenu will allow 
resetting of the minimum travel position of the 
drive (Set Pos 0%) and the CPS voltage at the 
minimum travel position (CPS Zero%).  Online 
help is available through the communication 
device.