GENERAL SPECIFICATIONS—ALL MODELS
Drive Power 
120 V ac single-phase 50 or 60 Hz 
Allowable Tolerance 
+10%
 
240 V ac single-phase 50 or 60 Hz 
 
-15%
 
Max. Current and Power
 
Model 
120 V ac 
240 V ac
 
11-159, -169 
.40 A 
48 W 
.20 A 
48 W
 
11-209, -269 
.65 A 
78 W 
.33 A 
78 W
 
11-309, -369 
.65 A 
78 W 
.33 A 
78 W
 
11-409, -469 
3.10 A 
400 W 
1.55 A 
400 W
Operating Conditions 
-40° to 185°F (-40° to 85°C) 
   
0 to 100% relative humidity
Communication Interface 
HART protocol (Rev. 5 -- burst mode is not supported), local pushbutton/
LED panel and RS-232 Serial commands.
Demand input Signal Options 
4–20 mA (1–5 V dc input is possible with the removal of the "R11"
  (DCM-2) 
resistor located on the DCM-2 board (see diagram on page 78).
Adjustability for Split Range 
0%:  0.1 V to 4 V dc
  Operation 
100%:  0% + 1 V  min. to 5 V max.
Step Size 
0.15% typical (configurable).
Linearity 
±1% of span, max. independent error
Hysteresis 
0.25% of span at any point
Demand input Signal   
Linear:  Drive output shaft moves proportionally to the input signal.
  Characterization 
Square:  Drive output shaft moves proportionally to the square of the
  
input 
signal.
   
Custom:  Drive output shaft moves according to the custom demand
   
response curve. 
 
   
Position Feedback Signal 
4–20 mA
  for Remote Indication 
 
Isolation 
Demand input and position Feedback signals are isolated from ground
    
and the ac power line.  Signal buffering provides 24 V dc isolation 
   
between the Demand and Feedback signals.
Action on Loss of Power 
Stays in place
Action on Loss of Input 
Stays in place or drives to any preset position (configurable).
 
Signal (Power On) 
 
 
 
 
Stall Protection  
If the motor tries to run in one direction for more than 300 seconds
 (Optional) 
(configurable from 30 to 300 seconds), the DCM-2 will shut off power 
to the motor (feature can be enabled/disabled).