“ A n a l o g   o u t p u t   1   a n d   i t s   d i g i t a l 
representation are outside the operating 
range limits, and not responding to input” 
“The Position Signal is less than –5% or 
greater than 105%”
“Position signal in LOS”
“Position out of accurate measurement 
range”
This is an additional standard HART
®
-defined message that 
appears whenever the HART
®
 primary variable (Position signal) 
is outside the design or calibrated range.  It accompanies the 
message above.
This is a Beck-specific message that appears after the HART
®
-
defined messages above.  It specifically pinpoints the position 
signal to the DCM-2 as the problem source, and indicates that the 
signal is outside the calibrated range limits.  The upper and lower 
limits are -5% and 105% of the calibrated range respectively.
This is a Beck-specific message that appears after the HART
®
-
defined messages above.  It specifically pinpoints the position 
signal to the DCM-2 as the problem source, and is intended to 
indicate a CPS or wiring failure.  The message is triggered when 
the position signal is outside the minimum and maximum limits 
of 0.25 V dc and 5.35 V dc respectively.  In this case, the LOS 
message above will also be present.
This is a Beck-specific message that appears after the HART
®
-
defined messages previously mentioned.  It specifically pinpoints 
the position signal to the DCM-2 as the problem source, and 
indicates that the signal is outside the 0.25–5.35 V dc design 
range.  The LOS message above will also be present when this 
message is present.
Miscellaneous Messages
Message
Description
“The Feedback Signal is enabled but the 
loop is open”
“Stall condition has been detected (see 
'Stall Time' in the 'General Setup' menu)”
"Feedback is in fixed mode"
This is a Beck-specific alarm message that alerts the user that 
external position feedback signal is installed and enabled, but 
not wired to an external load.  If the signal is wired to an external 
load and this message appears, it implies that a wiring failure 
somewhere between the drive and the monitoring device has 
occurred.  If the DCM-2 board is equipped with the feedback 
module, but the signal is not being used, this message can be 
eliminated by disabling the feedback in the configuration.
This is a Beck-specific alarm message alerting the user that the 
drive is in a stalled condition and is no longer trying to fight the 
load.  This condition occurs if the drive cannot reach the demand 
position in the ime allotted by the stall time setting (configurable 
from 30–300 seconds, default 300 sec.).  In drives equipped with 
optional torque measurement, this message may not occur due 
to the pre-emptive action of overtorque protection.
The "FB Out Test" diagnostic allows the user to set Feedback to 
a fixed value, rather than the normal mode of having Feedback 
follow the Position value.  If the Feedback value is left in the "fixed" 
mode, this error will be reported to alert the user that Feedback 
is not following the Position value.
Message
Description