 Dry Seasoned Wood Only!                                                              3-90-798                                                                 Save These Instructions
Oakleaf Woodburning stove
B.  Clearances To Combustibles
CLEARANCE TO COMBusTIBLEs: vertical venting Configuration 
Location
unit to side Wall 
   
17" / 432 mm
unit to Back Wall 
   
14" / 356 mm
vent Pipe to side Wall             26.75" / 679 mm
d*  
vent Pipe to Back Wall            *17.5" / 444 mm
CLEARANCE TO COMBusTIBLEs: vertical vent, Horizontal Exit 
Location 
A
C
B
d*
A
C
E
f
A
C
B
d
E
unit to side Wall 
   
16" / 407 mm
unit to Back Wall 
   
13" / 330 mm
vent Pipe to side Wall           25.25" / 641 mm
d* 
vent Pipe to Back Wall              *17" / 432 mm
E* 
vent Pipe to Ceiling   
*16" / 407 mm
Minimum vertical  
 
  0" /  0 mm
for clearance reduction methods, refer to NfPA 211 or Local Codes
Pipe clearance may be reduced using double wall 
or insulated connector pipe, provided that you 
adhere to the specified clearances from the stove 
itself. follow pipe manufacturer's guidelines.
Pipe clearance may be reduced using double wall 
or insulated connector pipe, provided that you 
adhere to the specified clearances from the stove 
itself. follow pipe manufacturer's guidelines.
* NfPA 211 specifies 18" clearance to 
single wall connector pipe. This lower 
clearance is based on actual safety 
test conditions.
* NfPA 211 specifies 18" clearance to 
single wall connector pipe. This lower 
clearance is based on actual safety 
test conditions.