First Firing of the Furnace 
Start the furnace following the instructions given in the “Operating Instructions“.  The initial pilot lighting may be difficult due to air 
trapped in the gas lines.  During initial firing of the furnace, residual manufacturing grease will bake-out and smoke will occur 
which is not a health danger. To prevent nuisance and operation of fire alarms, ventilate the room for the first two hours of 
operation. 
 
Checking the Gas Inlet Pressure 
The gas inlet pressure can be measured by connecting a test gauge to the connection provided on the gas valve.  (Figure 8 - A)  
Once installation is complete, the gas inlet pressure must be checked.  The minimum gas inlet pressure must be as shown in 
“Technical Data”.  After checking the gas inlet pressure, disconnect the test gauge and firmly tighten the screw of the gauge 
connection, then check for gas leaks. 
 
Checking the Gas Manifold Pressure 
The gas manifold pressure can be measured by connecting a test gauge to the connection provided on the gas valve. (Figure 8).  
The furnace comes set from the factory at the correct manifold gas pressure.  After the installation is completed, the gas 
manifold pressure must be checked both in Hi and Lo input.  The gas manifold pressure must be as shown in the “Technical 
Data”.  Differences of plus or minus 0.1 in. w.c. are accepted.  If the Hi or Lo gas manifold pressures are different from the 
values given in the “Technical Data” table, or are more than 0.1 in. w.c., shut off the furnace and contact a qualified service 
technician for correction.  For instructions about adjustment of the manifold Hi and Lo pressures, see the “Servicing” section.  
After checking the gas manifold pressure, disconnect the test gauge and firmly tighten the screw of the gauge connection and 
then check for gas leaks from it. 

 
 
 
Test Gauge Connection for Gas Inlet Pressure 
 
Test Gauge Connection for Gas Manifold Pressure 
 
Nut for Hi Pressure Adjustment (Pressure Regulator) 
Screw for Lo Pressure Adjustment (Hi – Lo Operator) 
 
Electric Clamp Connection 
 
Electric Cable Inlet 
 
 
Hole for Gas Supply Inlet 
 