Honeywell 805595 用户手册

下载
页码 46
IQ8Wireless transponder for wall mounting 
 
28 
FB 798941 / 10.06 
The installation location of the IQ8Wireless transponder should be chosen so that the shortest 
transmission path (wireless path) to the wireless bases can be implemented and that no 
electro-magnetic interference is to be expected. The function of the IQ8Wireless transponder 
may be seriously affected and its range reduced by interference sources or an unsuitable 
installation location: 
 
Electrical interference sources 
• 
Energy/power cables 
• 
Powerful wireless transmitters in the vicinity 
• 
Switched-mode electronic circuits 
• 
Computer and IT systems 
 
Mechanical interference sources 
• 
Metal grating and metal gates  
• 
Metal cabinets (cabinet units) 
• 
Concrete ceilings and concrete walls 
• 
Unfavourable arrangements (angles) of IQ8Wireless transponders and IQ8Wireless 
detector bases 
 
 
The IQ8Wireless transponder operates with a range up to 25 channels within the 
frequency band of 433 MHz and 868 MHz.  
Also consider temporary interference sources such as mobile phones or 
computers! 
 
 
Requirements for the environment 
• 
The quality of the wireless transmission depends very much on the ambient temperature. 
A reduction in temperature in the monitored rooms, for example at night may have a 
negative effect on the wireless quality achieved during the day. 
• 
Sliding gates or doors which are open during the day for operational reasons as well as 
overhead cranes may disrupt the wireless path when they are closed or in a different 
position respectively. 
 
 
To plan the wireless system the tools 8000 software contains a field strength 
measurement tool. This can be used to check the quality of the wireless link
(field strength) between the IQ8Wireless transponder and the IQ8Wireless 
devices.  
If used properly, the “IQ8Wireless transponder (Part No. 805595)“ complies with 
the basic directives and corresponding requirements in according to the 
R&TTE Directive 1999/5/EC.