MAINTENANCE
TESTING THE GROUND 
FAULT SENSOR
1.  Start the generator and allow it to warm up.
2.  Press the test button on the ground fault sensor 
(see Figure 62).
1
2
3
4
Figure 62 – Ground Fault Sensor Test
1 -  Test Button
2 -  Reset Button
3 -  Fault Light
4 -  Power Light
3. 
The light next to “fault” will light and the main 
breaker will trip.
4. 
If the main breaker does not trip, the ground 
fault sensor is not working correctly and must be 
repaired before the generator can be operated.
5. 
Press the reset button and reset the main breaker. 
The light next to “fault” will go out and the light next 
to “power” should light. Power will be restored to all 
outlets.
CLEANING THE GENERATOR
It is important to inspect and clean the generator before 
every use.
Clean All Engine Air Inlet and Outlet Ports – Make 
sure all engine air inlet and outlet ports are clean of any 
dirt and debris to ensure the engine does not run hot 
(see Figure 63 and Figure 64).
Figure 63 – Engine Air Inlet and Outlet Ports – 10KPRO
Figure 64 – Engine Air Inlet and Outlet Ports – 8KPRO