Bryant Legacy Line 124A 用户手册

下载
页码 32
3
PHYSICAL DATA
UNIT SIZE --- SERIES
018---C
024---D
030---D
036---C
042---D
048---C
060---C
Operating Weight lb (kg)
195 (88.4)
184 (83.5)
177 (80.3)
225 (102.1)
228 (103.4)
270 (122.5)
337 (152.9)
Shipping Weight lb (kg)
223 (101.2)
223 (101.2)
218 (98.9)
259 (117.5)
267 (121.1)
303 (137.4)
372 (168.7)
Compressor Type
Scroll
REFRIGERANT
Puron® (R---410A)
Control
TXV (Puron® Hard Shutoff)
Charge lb (kg)
5.4 (2.45)
5.48 (2.49)
5.8 (2.63)
6.97 (3.16)
9.5 (4.31)
11 (4.99)
13.3 (6.03)
COND FAN
Propeller Type, Direct Drive
Air Discharge
Vertical
Air Qty (CFM)
2235
3223
3223
3810
3810
3810
4050
Motor HP
1/12
1/12
1/12
1/5
1/5
1/5
1/4
Motor RPM
800
800
800
800
800
800
800
COND COIL
Face Area (Sq ft.)
19.40
17.60
17.60
22.63
17.60
20.12
30.18
Fins per In.
25
25
25
25
20
20
20
Rows
1
1
1
1
2
2
2
Circuits
3
4
4
5
7
7
7
VALVE CONNECT. (In. ID)
Vapor
5/8
5/8
3/4
3/4
7/8
7/8
7/8
Liquid
3/8
REFRIGERANT TUBES (In. OD)
Rated Vapor*
5/8
3/4
7/8
1---1/8
Liquid
3/8
*Units are rated with 25 ft (7.6 m) of lineset length. See
Vapor Line Sizing and Cooling Capacity Loss table when using other sizes and lengths of lineset.
VAPOR LINE SIZING AND COOLING CAPACITY LOSS
LONG LINE APPLICATION: An application is considered
”Long line” when the total equivalent tubing length exceeds 80
ft. (24.38 m) or when there is more than 20 ft. (6.09 m) vertical
separation between indoor and outdoor units. These applications
require additional accessories and system modifications for
reliable system operation. The maximum allowable total
equivalent length is up to 250 ft. (76.2 m). The maximum
vertical separation is 200 ft. (60.96 m) when outdoor unit is
above indoor unit, and up to 80 ft. (24.38 m) when the outdoor
unit is below the indoor unit. Refer to Accessory Usage Guideline
below for required accessories. See Longline Application
Guideline for required piping and system modifications. Also,
refer to the table below for the vapor tube diameters based on the
total length to minimize the cooling capacity loss.
Unit
Nominal
Size
(Btuh)
Maximum
Liquid Line
Diameters
(In. OD)
Vapor Line
Diameters
(In. OD)
Cooling Capacity Loss (%)
Total Equivalent Line Length ft. (m)
Standard
Application
Long Line Application Requires Accessories
26---50
(7.9---15.2)
51---80
(15.5---24.4)
81---100
(24.7---30.5)
101---125
(30.8---38.1)
126---150
(38.4---45.7)
151---175
(46.0---53.3)
176---200
(53.6---61.0)
201---225
(61.3---68.6)
226---250
(68.9---76.2)
18000
1 Stage
Puron AC
3/8
1/2
1
2
3
4
6
7
8
9
10
5/8
0
0
1
1
1
2
2
3
3
24000
1 Stage
Puron AC
3/8
5/8
0
1
1
2
3
3
4
4
5
3/4
0
0
0
0
1
1
1
1
1
7/8
0
0
0
0
0
0
0
0
0
30000
1 Stage
Puron AC
3/8
5/8
1
2
3
3
4
5
6
7
8
3/4
0
0
1
1
1
2
2
2
3
7/8
0
0
0
0
1
1
1
1
1
36000
1 Stage
Puron AC
3/8
5/8
1
2
4
5
6
7
9
10
11
3/4
0
0
1
1
2
2
3
3
4
7/8
0
0
0
0
1
1
1
1
2
42000
1 Stage
Puron AC
3/8
3/4
0
1
2
2
3
4
4
5
6
7/8
0
0
1
1
1
2
2
2
3
1 1/8
0
0
0
0
0
0
0
0
0
48000
1 Stage
Puron AC
3/8
3/4
0
1
2
3
4
5
5
6
7
7/8
0
0
1
1
2
2
2
3
3
1 1/8
0
0
0
0
0
0
0
1
1
60000
1 Stage
Puron AC
3/8
3/4
1
2
4
5
6
7
9
10
11
7/8
0
1
2
2
3
4
4
5
5
1 1/8
0
0
0
1
1
1
1
1
1
Applications in this area are long line. Accessories are required as shown recommended on Long Line Application Guidelines
Applications in this area may have height restrictions that limit allowable total equivalent length, when outdoor unit is below indoor unit See Long Line Applica-
tion Guidelines
124A