14
TORQUE VALUES
Pump Size
Tie Rod Nuts
Vent and Drain
 
1SV 
22 lbs ft (30 N .m) 
15 lbs ft (20 N .m)
 
2SV 
22 lbs ft (30 N .m) 
15 lbs ft (20 N .m)
 
3SV 
37 lbs ft (50 N .m) 
15 lbs ft (20 N .m)
 
4SV 
37 lbs ft (50 N .m) 
15 lbs ft (20 N .m)
  33, 46, 
44 lbs ft (60 N .m) 
29 lbs ft (40 N .m)
 
  66, 92SV 
11. System head too high.
12. NPSHA too low – excessive suction lift or losses.
13. Discharge head too low – excessive flow rate.
14. Fluid viscosity, specific gravity too high.
15. Worn bearing.
16. Pump, motor or piping loose.
TORQUE VALUES
HP
 Motor
Motor Bolt
Adapter Flange
Coupling
Frame
1-4SV
33-92SV
  ¾ 
56C 
20 lbs ft (27 N .m) 
– 
15 lbs ft (20 N .m)
  1 
56C 
20 lbs ft (27 N .m) 
– 
15 lbs ft (20 N .m)
  1½ 
56C 
20 lbs ft (27 N .m) 
– 
15 lbs ft (20 N .m)
  2 
56C 
20 lbs ft (27 N .m) 
– 
15 lbs ft (20 N .m)
  3 
56C 
20 lbs ft (27 N .m) 
– 
15 lbs ft (20 N .m)
  5 
184TC  20 lbs ft (27 N .m) 
– 
15 lbs ft (20 N .m)  37 lbs ft (50 N .m)
  7½ 
184TC  20 lbs ft (27 N .m) 
– 
15 lbs ft (20 N .m)  37 lbs ft (50 N .m)
 
10
 
213TC 
45 lbs ft (61 N .m)  30 lbs ft (40 N .m)  30 lbs ft (40 N .m)  48 lbs ft (65 N .m)
 
 
215TC
 
15
 
215TC 
45 lbs ft (61 N .m)
  30 lbs ft (40 N .m)  30 lbs ft (40 N .m)  48 lbs ft (65 N .m)
 
 
254 TC 
 
48 lbs ft (65 N .m)  48 lbs ft (65 N .m)
 
20
 
254TC 
45 lbs ft (61 N .m)  48 lbs ft (65 N .m)  48 lbs ft (65 N .m)  48 lbs ft (65 N .m)
 
 
256TC
 
25
 
256TC 
45 lbs ft (61 N .m)  48 lbs ft (65 N .m)  48 lbs ft (65 N .m)  48 lbs ft (65 N .m)
 
 
284TC
 
30
 
284TC 
45 lbs ft (61 N .m)  48 lbs ft (65 N .m)  48 lbs ft (65 N .m)  48 lbs ft (65 N .m)
 
 
286TC
 
40
 
284TC 
45 lbs ft (61 N .m)  48 lbs ft (65 N .m) 
 
48 lbs ft (65 N .m)
 
 
286TC
 
50
  324TSC 
45 lbs ft (61 N .m)  48 lbs ft (65 N .m) 
 
48 lbs ft (65 N .m)
 
 
326TSC
 
60
  326TSC 
45 lbs ft (61 N .m)  48 lbs ft (65 N .m) 
 
48 lbs ft (65 N .m)
 
 
364TSC
 
75
 
365TSC
 
45 lbs ft (61 N .m)  48 lbs ft (65 N .m) 
 
48 lbs ft (65 N .m)
 
 
NOTE: Discharge loop must be high enough to keep liquid in the bottom stages during shut-down.