Meaning of LED and ALARM
STATUS LED COLOR
ALARM SOUNDS
STATUS CONDITION
Green
X
City power normal and battery full
Green BlinkingX
City power normal and battery charg
ing
Yellow Blinking1 Time 2 Sec
City power loss
Yellow Blinking1 Time 1 Sec
City power loss & battery low
Red 
City power loss and battery low –
Or the GN-675VA has been shut down.
Yellow 25%
Battery charged 25%
Yellow 50%
Battery charged 50%
Yellow 75%
Battery charged 75%
Yellow 100%
Battery charged 100%
Importance Notices:
• Read instructions carefully before operating the GN-675VA UPS.
• All operation instructions should be followed.
• The GN-675VA should be power by a grounded power source.  
DO NOT OPERATE THE GN-675VA WITHOUT a grounded power source.
• Replace fuse with the same type and rating only.
Warning:
• Don’t open the cover, there are no user serviceable parts inside.
• Don’t insert any object into ventilation holes or other openings.
• The GN-675VA is for computer use only.
System Function:
• Automatic voltage regulator. Built-in line conditioner provides stable 
voltage when power fluctuates. 
• Monitoring software allows the user to view status of the GN-675VA
• Modem (modem line) protection.
• Overload and short current protection.
• Automatically detect circuit and battery charge / discharge protection.
w w w . g e n i c a . c o m
Electrical Specification
Inverter Capacity:
675VA
AC Input
110V +/- 20% 60Hz
Inverter Output (rms)
100VAC or 120VAC
Inverter Regulation
+/- 3%
Cosine
0.6
Inverter Frequency
50 or 60Hz + 2%
Transfer Time
-< 3ms
Full Load Back-up Time
3 minutes
Battery Specification
7AH / 12V x 1
Operation Instructions (FOR US / 110V use ONLY)
• Make sure that you are plugging the unit into 110v wall outlet 
(city power) and that the power switch is in “O” position.
• Plug AC (power) cord into the outlet and plug the power cord 
of the computer and peripherals into the female outlet of the 
GN-675VA.
• Turn the power switch on back of the GN-675VA in the “I” position
and wait for about 3 seconds (soft start).  Now the UPS is in AC
operation mode and DC inverter output is in “stand by” mode.
• When AC input power is interrupted (AC power failure) the led will
start blinking yellow, and an alarm will sound. The GN-675VA will
switch to battery operation mode automatically.
CAUTION: After initial start-up, keep power on continuously to the GN-
675VA for at least 12 hours to ensure batteries are fully charged.