All machine adjustments & maintenance shall 
only be done after the machine’s power switch 
has been put in the “OFF” position & the 
power supply cord completely disconnected.
WARNING: Always make sure the unit is  
connected to a properly grounded electrical 
outlet. Failure to comply with this warning 
could result in serious bodily injury or death!
WARNING: DO NOT operate on low voltage! 
Low voltage causes loss of power, motor  
overheating, and possibly motor winding  
burnout. Voltage should be checked at the 
motor while it is operating.
•  Make sure that the extension cord length is  
properly sized for the motor used on this saw.  
See the chart in Section 2 of this document.
•  Single phase 1-1/2 hp motors are factory wired 
for 115 volt service and furnished with the correct 
NEMA configuration Plug (LL) [See FIG. 1] on the 
motor pigtail. See Table 1 below for the proper 
matching connectors:
Table 1
Electric Motor Plugs & Connectors
Motor
Wired for 
Voltage
Motor Pigtail 
Plug
(NEMA No.)
Connector 
Required 
(NEMA No.)
1-1/2 HP
115 V
L5-20P
L5-20R
1-1/2 HP
230 V
L6-15P
L6-15R
   For operator convenience, the 1-1/2 hp motor has 
Voltage Change Switch (J) [See FIG. 5] that allows 
operation on a 115 VAC or a 230 VAC power source.
The Voltage Change Switch (J) is mounted on the 
terminal box of the motor and must be set to either 
115, or 230 Volt, to match the voltage supply. Make 
sure that the Voltage Change Lock Bolt (TT) is in 
position. It will prevent the Voltage Change Switch 
[See FIG. 5] from being accidentally moved into the 
wrong position.
WARNING: The Voltage Change Switch (J) 
position is never to be changed while the 
motor is running. Make sure that the Voltage 
Change Lock Bolt (TT) is in position. It will pre-
vent the Voltage Change Switch from being 
accidentally moved into the wrong position.
•  Local electrical codes may require changing the plug 
on the motor to the proper NEMA connector to 
match the voltage supply.
•  The operator must use plug and receptacle  
connectors on all power cords (machine and  
extension), designed and approved for the selected 
motor voltage and equal to or greater than the 
rated motor full load current.
  The service receptacle, branch circuit conductors, 
and overcurrent protection shall have an ampere 
rating equal to or greater than the motor full load 
current. According to the National Electrical Code if 
the branch circuit has two or more receptacles, each 
receptacle has a maximum load ampere rating 
equal to 80% of the receptacle’s rating.
When this machine is set up to operate on 115 VAC, the 
motor has a full load rating of 19 amperes. This means 
that when operating this machine on 115VAC, it can only 
be used on a branch circuit with ONE 20-ampere rated 
receptacle. 
If the circuit has two or more 20-ampere 
receptacles, they each have load rating of 16 amperes 
and cannot be used by this machine.
•  The extension cord(s) used must have a voltage rating  
greater than the selected voltage (115 or 230) and be  
sized for the rated motor full load amps (as marked  
on motor specification plate).
•  Good motor performance depends on proper voltage. 
Extension cords that are too long and / or too small  
reduce the voltage to a motor under load. Operating  
below this minimum voltage will cause an increase  
in motor current resulting in slow startup, and  
overheating in the motor and controls. Sustained  
operation under these conditions will result in  
permanent damage to the motor and controls.
•  Long extension cords will probably have to be over 
sized to minimize the voltage drop to the machine.  
The size of the extension cord is dependent on the 
total conductor length (all extension cords) & the  
quality of the power source. The power cord size  
shall be capable of supplying a minimum of 90%  
of the motor nameplate voltage
 at the motor, when 
the motor is running rated full load.
•  Make sure that the extension cord length is properly 
sized for the motor used on this machine. Use exten-
sion cords NO SMALLER than the sizes indicated in 
Table 2 below:
Table 2
EXTENSION CORD SIZE (Minimum)
MOTOR
HP
50 ft Long
75 ft Long
100 ft Long
120 V 230 V 120 V 230 V 120 V 230 V
1-1/2
# 12
# 14
# 10
# 14
# 8
# 14
•  The branch circuit must have overcurrent protection  
in the form of a circuit breaker or fuses. The purpose  
of the overcurrent protection is to limit the current  
in the branch circuit conductors and connections to  
an amount equal to or less than their ratings. This  
is to prevent overheating that can lead to damage