• As depicted in Figure 1, place the baseplate on wedges, 
locating two wedges at each foundation bolt location. A gap 
of ¾" to 1½" (19 mm to 64 mm) is recommended between 
the baseplate and the foundation for grouting. Adjust the 
wedges as necessary to level the baseplate.
• Inspect baseplate for any distortion, and adjust as neces-
sary. Make sure that any necessary fi nal coupling alignments 
are possible within the motor movements and shim limits. 
Tighten the 4 foundation bolts fi nger tight.
• Build a dam around foundation and pour grout under the 
baseplate, insuring that the areas under the pump and  
motor are fi lled completely.
• Allow grout to harden for 48 hours before tightening  
4 foundation bolts.
Piping – General
• For maximum pump capacity, piping should not be smaller 
than the pump suction and discharge.
• To minimize pipe friction losses, avoid unnecessary pipe 
and fi ttings.
• All piping MUST be independently supported and MUST 
NOT place any piping loads on pump.
NOTICE: DO NOT FORCE PIPING INTO PLACE AT  
 
PUMP SUCTION AND DISCHARGE    
 CONNECTIONS.
Piping – Suction
• Short and direct suction piping is recommended. For  
suction lifts of over 10' (3 m) and liquid temperatures over 
120° F (49° C), consult pump performance curve for net 
positive head required (NPSH
R
).
• If a pipe size larger than the pump suction is required, an 
eccentric pipe reducer, with the straight side up, MUST  
be installed at the pump suction.
• If the pump is installed below the liquid source, install a full 
fl ow isolation valve in the suction for pump inspection and 
maintenance.
NOTICE: DO NOT USE THE ISOLATION VALVE TO  
 
THROTTLE PUMP. THIS MAY CAUSE LOSS  
 
OF PRIME, EXCESSIVE TEMPERATURES  
 
AND DAMAGE TO PUMP, VOIDING    
 WARRANTY.
• If pump must be installed above the liquid source, the  
following MUST be provided:
• To avoid air pockets, no part of the piping should be 
above the pump suction connection.
• Slope the piping upward from liquid source.
• All pipe joints MUST be airtight.
• Use a foot valve ONLY if necessary for priming or to 
hold prime during intermittent duty.
• The suction strainer or suction bell MUST be at least  
3 times the suction pipe diameter area.
• Insure that the size and minimum submergence over suc-
tion inlet is suffi cient to prevent air from entering pump 
through a suction vortex. See Figures 2 through 5.
Piping – Discharge
• Install a check valve, suitable to handle the fl ow and liquids, 
to prevent backfl ow. After the check valve install an   
appropriately sized gate valve to be used to regulate the 
pump capacity, pump inspection and maintenance.
• When required, the pipe increaser should be installed be-
tween the check valve and the pump discharge.
Wiring and Grounding
DISCONNECT AND LOCKOUT 
THE ELECTRICAL POWER BEFORE 
ATTEMPTING ANY MAINTENANCE. 
FAILURE TO DO SO CAN CAUSE A 
SHOCK, BURN OR DEATH.
• All wiring and grounding connections must be in accor-
dance with Local and National Electrical Code require-
ments.
• Use only stranded copper wire to the motor and ground. 
Wire size MUST limit the maximum voltage drop to 10%  
of  the motor nameplate voltage, at the motor terminals. 
Excessive voltage drop may affect performance and will 
void the motor warranty.
• Single phase motors supplied by Goulds, have built in ther-
mal overloads. Other motors not so equipped MUST  
use a properly sized contactor and overload. Fuses are 
permissible.
• Three phase motors require all leg protection with properly 
sized magnetic starters and thermal overloads.
WARNING
Hazardous
voltage
 
Figure 4 
Figure 5
Sleeve
Washer
Lug
Top of foundation –
clean and wet down
Grout
Leveling wedges or shims – left in place
Base
Grout hole
(
1
/
4
")
Finished grouting
(
1
/
2
 to 
3
/
4
")
Allowance
for leveling
Wood
frame
H min.
D
D
H min.
D
D
1.5D
min.
3.0D
min.
H min.
D  min.
2
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
H = Min. Submergence in feet
H
1 2 3 4 5 6 7 8 9 10111213141516
V
V = Velocity in feet per second
= GPM x 0.321
Area
GPM x 0.4085
D
2
 
Figure 2 
Figure 3