White Rodgers 47D40-801 安装指导

下载
页码 4
2
SPECIFICATIONS 
Electrical Ratings [@ 77
F (25
C)]:
Rated Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   24 VAC 
Rated Voltage Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   18-30 VAC
Max. Power Consumption @ 24 VAC   . . . . . . . . . . . . . . . . . .   4.08 VA
Nominal Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   50/60 Hz
Relay Load Ratings:
  Compressor Contactor Relay  . . . . . . . . . . . . . . . . . . . . . .    20 VA in rush, 6 VA holding
  Fan Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   1/2 HP @ 240, 1/4 HP @ 120 VAC
  Reversing Valve Relay (RV) . . . . . . . . . . . . . . . . . . . . . . . .   24 VA
  Auxiliary Heat Relay (D). . . . . . . . . . . . . . . . . . . . . . . . . . .   1 Amp. 0.6 P.F.
Operating Temperature Range . . . . . . . . . . . . . . . . . . . . . . . .   -40
o
 to 150
F (-40
to 65
C)
Humidity Range  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .   5% to 95% relative humidity 
                                                                                                   (non-condensing)
Timing Specifications @ 60Hz*
Nom
Units
Defrost Lockout Time
34
Mins.
Maximum Defrost Time
14
Mins.
Transient Delay
2
Mins.
Maximum Frosting Time
6
Hrs.
Short Cycle Lockout Time 
5
Mins.
Noise Abatement Time 
5
Sec.
*50Hz Timings are 20% longer.
The control is recognized by UL as an incorporated 
electronics control per UL 60730-1A. This control does 
not perform any safety/protective functions. This device is 
automatic, type 1 action, incorporated control.
OPERATION 
Each controller has 24 VAC input and B, Y, and D terminals 
for connection to a standard thermostat. The controller has 
pins for connection of two temperature sensors to measure 
ambient and coil temperature. Controlled outputs are outdoor 
fan, reversing valve, and compressor contactor. 
The controller has a LED to indicate system operation status.
Option Switch
Switch labeled SW1 is used to select the defrost mode 
termination temperature of outdoor coil. Defrost mode is 
terminated when the coil temperature exceeds the selected 
termination temperature. Temperature options for SW1 switch 
settings are:
LED
Fault Indication
Display Priority
ON
Normal
0
1 Flash
Defrost mode
1
2 Flashes
Coil sensor fault
3
3 Flashes
Ambient sensor fault
2
Short Cycle Protection
The control includes protection against short cycling the 
compressor. At power-up, and each time the Y input is 
interrupted, the control will enter a 5-minute short cycle 
lockout period. During this lockout, the control will not 
energize the compressor contactor, even if a call for heating 
or cooling is received on the Y input. The control will resume 
normal operation when the lockout period expires.
Noise Abatement
When the reversing valve is switched during an active call for 
heating or cooling, such as when entering or leaving a defrost 
cycle, the control will de-energize the compressor contactor 
for 5 seconds in order to reduce compressor noise.
Diagnostic Features
The control continuously monitors system operation. If a fault 
occurs, the red LED on the control will flash a diagnostic 
code, if more than one fault occurs, only the code with the 
higher priority will flash. The flash time is to be 0.5 seconds 
on and 0.5 seconds off followed by 2 seconds off. The table 
shows the diagnostic codes:
B
A
On
Off
50
F
Off
On
60
F
On
On
70
F
 
(default)
Off
Off
80
F
B A
B A
B A
B A
Test Pins
The connector  labeled 
TEST can be used to change 
operation mode in the field. Momentarily short the test pins 
to force the system into the defrost mode. Momentarily short 
the test pins again to terminate the defrost mode. To avoid 
unnecessary system mode transition, do not use the test pins 
frequently.