Overview
The 10-175UL is a power limited power supply/charger that will convert 115VAC / 60Hz
input, into two individually PTC protected 12VDC or 24VDC output, (see specifications).
They are intended for use in applications requiring UL Listing for Access Control (UL294)
and applications requiring an interface with Fire Alarm Control Panels. It must be installed
in accordance with National and Local Electrical Codes and Regulations.
Specifications
UL listed Access Control (UL294)
CSFM approved - California State Fire Marshal
MEA approved - NYC Dept. of Buildings 18-98-E
NFPA 101 (Life Safety)
Input 115VAC/60 Hz, .6 amps
Switch selectable 12VDC or 24VDC power limited output
1.75 amps continuous supply current @ 12VDC or 24VDC
Latching fire alarm tie-in with manual reset
Filtered and electronically regulated output
Charge current: 0.4 amps Max
Aux relay output: (form “C”, 1 amp, 28VDC)
AC Fail output relay (form “C” 1 amp, 28VDC)
Enclosure Dimensions: 15.5”H x 12”W x 4.5”D
Output Specifications
Output VDC Switch Position
Max. Stand-by
Max. Alarm
Battery
Load DC
Load DC
(Optional)
12VDC
SW1 Open
1.75 amps
1.75 amps
12VDC
24VDC
SW1 Open
1.75 amps
1.75amps
24VDC
Stand-By Specifications
Output 
4Hr. of Stand-by & 5 minutes of alarm
12VDC / 7 AH Battery
Stand-by = 1.25 amps
24VDC / 7 AH Battery
Alarm = 1.25 amps