Utica Boilers H2OBT 安装指导

下载
页码 8
3
II. IMPORTANT SAFETY INSTRUCTIONS
WARNING – When using electrical appliances, basic safety precautions to reduce the risk of fire, electric 
shock, or injury to persons should be followed, including:
READ ALL INSTRUCTIONS BEFORE USING THIS BUFFER TANK.
1.  This tank must be grounded if any electrical control is used. Connect only to properly grounded outlet. 
2.  Install or locate this buffer tank only in accordance with the provided installation instructions
3.  Use this tank only for its intended use as described in this manual.
4.  As with any appliance, close supervision is necessary when used by children.
5.  This tank should be serviced only by qualified personnel. Contact nearest authorized service facility for 
examination, repair, or adjustment.
SAVE THESE INSTRUCTIONS
III. Application
The primary application of a buffer tank is to reduce heat pump, chiller, or boiler short cycling. Hydronic buffer tanks are 
used in systems operating below the design load condition, which is most of the time, or in systems having several low 
BTU cooling or heating loads calling at different times. This can cause the heat pump or the boiler to short cycle, resulting 
in reduced operating efficiency and shorter equipment life. 
The hydronic buffer tanks are built with 4 connections. Two connections can be piped to the heat pump or boiler, and two 
connections can be piped to the distribution system. If piped correctly, the tank can serve as both a thermal buffer and a 
hydraulic separator. The heat pump or boiler can be hydraulically decoupled from the distribution system. The tanks are all 
stainless steel construction with R-12 insulation, and an ABS jacket. 
A 3/8” ID thermal well is located mid-tank. Thermistors to be inserted 3” into the well, or the well will accept the Honey-
well L4006A controls.
WARNING:
Do not operate the water heaters in areas where the Ph is above 8.0 or below 6.0, and/or with chloride concentrations 
greater than 100 parts per million (ppm). ECR’s standard warranty does not cover problems caused by improper water Ph 
or excessive levels of chlorides.
DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
If you smell gas vapors, DO NOT try to operate any appliance - DO NOT touch any electrical switch or use any phone in 
the building. Immediately, call the gas supplier from a remote located phone. Follow the gas supplier’s instructions or if the 
supplier is unavailable, contact the fire department.