Utica Boilers SFH-W IV 安装指导

下载
页码 28
16
INSPECT CHIMNEY  to verify it is constructed according 
to latest revision of the NFPA 211. Local codes may differ 
from this code and should be checked. Where there is a 
conflict, local code will prevail.  
• Boiler must be installed into chimney which has 
masonry or metallic chimney liner.
• Unlined chimney will have leaks that will cause poor 
chimney performance (NO DRAFT), and could result in 
positive pressure in combustion chamber.
• Horizontal portions of venting system should not 
exceed 10 feet in length. Horizontal lengths over 10 
feet will have negative effect on chimney performance.
• Chimney should extend at least 2 feet above any 
portion of building within 10 feet. See Figure #15. It 
should produce negative draft of .06 to .08 inches of 
water column, (W.C.), as measured with draft gauge 
between boiler and barometric draft control while 
maintaining .02 inch W.C. negative draft in combustion 
chamber. See chart “Chimney or Vent Sizes” for 
recommended chimney or vent sizes. 
• Inadequate draft will cause improper combustion, 
resulting in dirty flue ways and high fuel bills. 
CONNECT FLUE PIPE same size as boiler outlet to 
chimney, sloping upward continuously toward chimney 
approximately ¼” per foot. Bolt or screw joints together to 
avoid sag.
If oil fired water heater is vented into same flue as 
boiler, provide separate hole into chimney whenever 
possible. When not possible, use “Y” connection in 
flue pipe, using separate draft regulator for each unit. 
When chimney will not provide adequate draft 
to handle input from water heater and boiler 
simultaneously, wire units so that only one will 
operate at a time, favoring water heater.
VENTING SYSTEM INSPECTION & INSTALLATION
Figure #15