Utica Boilers SFE IV Steam 安装指导

下载
页码 24
19
Impurities in boiler water of a steam boiler may cause 
foaming and an unsteady water line, or prevent steam 
generation. They may result in objectionable odors 
escaping from the vents on water boilers. This condition 
is caused by oil, grease, and sediment from pipe fittings 
collecting within the boiler and can be remedied only by 
giving the boiler a thorough cleaning.
BOILERS SHOULD BE CLEANED BY SKIMMING OR 
BLOWING DOWN. 
NOTICE
Do not leave Boiler unattended during cleaning/
skimming process.
Skimming Off Impurities
Some of the impurities in the boiler water will float on the 
water and must be skimmed off.
With the boiler empty and cool, slowly begin to add water. 
After water has entered boiler - never before - turn “on” 
oil burner  and adjust water flow so that the water being 
added is kept just below boiling point. Avoid boiling and 
turbulence.
Gradually raise hot water level to skimming hole (Figure #7)  
installed  on  the rear section of the boiler being careful not to 
raise it above the opening of the hole. Skim until there are no 
impurities. Repeat the process if necessary.
Water may be checked to make sure it is free from oil by 
drawing off a sample at the skimming hole. If the sample 
is reasonably free from oil, it will not froth when boiled on 
stove. This test does not indicate the amount of  sediment 
which may lay in the bottom of the boiler. It is therefore 
necessary that the boiler be further cleaned by “blowing 
down.”
Blowing Down The Boiler
Before blowing down the boiler, fill it to the water line. 
Turn on burner and allow five pounds of steam pressure to 
build up. Run a temporary connection from one of the drain 
valves to a nearby sewer. Connect to a drain valve on the 
opposite end of the boiler from feed water inlet, if possible. 
Shut off the oil burner, open drain valve and blow down the 
entire contents of boiler.
Allow boiler to thoroughly cool and slowly refill to water 
line. Repeat as many times as required until blow off water 
is clear. Owner should blow down boiler at least once each 
month of the heating season.
Before seasonal start up it is advisable to have a qualified 
service agency check boiler for soot and scale in flues, 
change oil filter and nozzle, clean burner and re-adjust 
burner input rate to maintain proper operation and high 
operating efficiency.
On steam boilers verify boiler is filled to water line as 
indicated in Figure #14. Gauge valves should be normally 
open. To remove dirt from gauge glass petcock may be 
opened to flush out the glass.
Radiator valves on one-pipe steam system must be either 
wide open or tightly shut. Do not attempt to regulate room 
temperature by partially closing the radiator valve.
Air vents on steam radiators and the supply main release 
air from the system. If radiators do not heat satisfactorily, 
make sure the air vents are clean and operational.
The lever of the pressure relief valve on the boiler (Figure 
#14) should be operated periodically to make sure that it 
is functioning properly.
Safety valve should open before the steam pressure 
exceeds the 15 psi. reading on the gauge. (Figure #14) 
If this pressure is exceeded and the safety valve does not 
open, it must be replaced. If the safety valve leaks steam 
when the boiler is operating at  normal pressures, it should 
be immediately replaced. Corrosion can build up rapidly 
at the valve seat and prevent its functioning as a safety 
device.
If the water in a steam boiler appears to be dirty or oily, or 
the water level in the gauge glass fluctuates considerably, 
the boiler should be cleaned. A competent service person 
will use approved cleaning compounds and properly clean 
and flush out the boiler. He/she should also clean or replace 
air vents and traps, clean flue passages and check for 
proper operation of all controls and safety devices.
The venting system should be inspected at the start of each 
heating season. Check the vent pipe from the boiler to the 
chimney for signs of deterioration by rust or sagging joints. 
Repair if necessary.
MAINTENANCE PROCEDURES
 WARNING
Burn and scald hazard.  Verify Boiler is off and 
cooled before performing maintenance. Have a 
qualified service agent perform maintenance. Failure 
to follow these instructions could result in death or 
serious injury.
!