APPENDIX A - CONTROL MODULE
STEP 3: Check spark ignition circuit. 
Disconnect ignition cable at SPARK terminal on module.
WARNING
Electrical shock hazard. Ignition circuit generates 
over 10,000 volts. Turn OFF electrical power 
supply at service panel before making electrical  
connections.  Failure to do so could result in death 
or serious injury.
!
  
Energize module and listen for audible sparking noise. 
When operating normally, there should be a buzzing noise 
that turns on and off twice per second for duration of 1–7 
seconds depending on model.
STEP 4: Verify pilot and main burner lightoff.
• Initiate call for heat. Turn thermostat above room 
temperature.  Ignition sequence may be delayed by 
thermal purge until boiler water temperature is below 
140°F (60°C)
• Watch pilot burner during ignition sequence.  
— Verify ignition spark continues after pilot is lit.
— Verify pilot lights and spark stops, verify main  
burner does not light.
• If so, ensure adequate flame current as follows.
— Turn off boiler at circuit breaker or fuse box.
— Clean flame rod with emery cloth.
— Verify electrical connections are clean and tight. 
Replace damaged wire..
— Check for cracked ceramic insulator, which can 
cause short to ground, and replace igniter-sensor if 
necessary.
— At gas valve, disconnect main valve wire from MV 
terminal.
— Turn on power and set thermostat to call for heat. Pilot 
should light, main burner will remain off because main 
valve actuator is disconnected.
— Check pilot flame. Verify it is blue, steady and 
envelops 3/8 to 1/2 in. [10 to 13 mm] of flame rod. 
See Figure 24 for possible flame problems and causes. 
— If necessary, adjust pilot flame by turning pilot 
adjustment screw on gas control clockwise to decrease 
or counterclockwise to increase pilot flame. Following 
adjustment, always replace pilot adjustment cover 
screw and tighten firmly to assure proper gas control 
operation. Figure 16, page 19. 
— Set temperature below room set-point to end call for 
heat.
• Recheck ignition sequence as follows.
— Reconnect main valve wire.
— Adjust thermostat above room temperature.
— Verify ignition sequence at burner.
— If spark does not stop after pilot lights, replace 
module.
— If main burner does not light or if main burner lights 
and system locks out, check module, ground wire and 
gas control as described in troubleshooting table. See 
Table 6, Page 24.
Figure 24 - Troubleshooting Pilot Flame
Correct Pilot Flame: 3/8 to 1/2 inch in flame. 
See Figure 20, Page 21.