10 - ELECTRICAL WIRING
Electrically bond boiler to ground in accordance with       
requirements of authority having jurisdiction.  Refer 
to National Electrical Code, ANSI/NFPA 70.
ELECTRIC POWER SUPPLY
Run separate 120 volt circuit from separate over 
current protective device in electrical service entrance 
panel. This should be a 15 ampere circuit. Locate 
shut-off switch at boiler. It must be turned off during 
any maintenance. Connect 120 volt power supply to 
control leads L1 (HOT) and L2.
LWCO kit 550002998 includes wiring instructions and 
diagrams. If using another LWCO, refer to specific 
manufacturer instructions supplied by appropriate 
manufacturer.
Run a 14 gauge or heavier copper wire from boiler 
to grounded connection in service panel or properly 
driven and electrically grounded ground rod.
THERMOSTAT INSTALLATION
1. 
Thermostat should be installed on an inside wall 
about four feet above the floor.
2. 
NEVER install thermostat on outside wall. 
3. 
Do not install a thermostat where it will be 
affected by drafts, hot or cold pipes, sunlight, 
lighting fixtures, televisions, a fireplace, or a 
chimney.
4. 
Check thermostat operation by raising and 
lowering thermostat setting as required to start 
and stop the burners.
5. 
Instructions for the final adjustment of the 
thermostat are packaged with the thermostat 
(adjusting heating anticipator, calibration, etc.)
Set heat anticipator at .2 amps. 24 volt thermostat 
connects to aquastat terminals T and TV.
WARNING
Electrical shock hazard.  Turn OFF electrical 
power supply at service panel before making 
electrical  connections.  Failure to do so could 
result in death or serious injury.
!
  
NOTICE
Label all wires prior to disconnection when 
servicing controls. Wiring errors can cause 
improper and dangerous operation. Verify 
proper operation after servicing.
VENT DAMPER WIRING
Boiler is equipped with factory wired harness with 4 
pin molex plug, that plugs into 4 pin molex receptacle 
inside vent damper operator.
Vent damper must be connected for boiler to operate.
If any of the original wire as supplied with this 
appliance must be replaced,
It must be replaced with type 105°C thermoplastic 
wire or its equivalent.