15 - MAINTAINING YOUR BOILER
BURNERS
Beginning of heating season visually check pilot end 
main burner flames. See Figure 16.
SAFETY RELIEF VALVE
Refer to page 7 for important information. To test 
safety relief valve refer to valve manufacturer’s in-
structions packaged with relief valve. Call Technical 
Support if manufacturer’s instruction are not located.
EXPANSION TANK
Tank may become waterlogged, or may receive 
excess of air. Frequent automatic opening of safety 
relief valve indicates water logging. High boiler 
temperature accompanied by unusually low radiation 
unit temperature (and “knocking”) indicates excess 
air in tank.
To correct:
1. 
Close valve between boiler and tank. Drain tank 
until empty. 
2. 
Check all tank plugs and fittings. Tighten as 
necessary. 
3. 
Open valve between boiler and tank. Water 
will rise to normal height in tank if you have 
automatic fill valve (otherwise, manually refill 
system).
BOILER FLUE PASSAGES
Recommend following checked annually by qualified 
service agent. 
• flue passages 
• burner adjustment
• operation of controls
Before start of each season (or whenever system 
has been shut down for some time) recheck whole 
system for leaks and recheck boiler and vent pipe 
for leaks. Replace or patch any boiler seals that are 
faulty.
VENT PIPE
Venting and piping should be checked at least once 
a season. If vent piping shows any sign of leaking, 
replace immediately. 
WATER SYSTEM
If system is to remain out of service during freezing 
weather, always drain it completely (water left in to 
freeze will crack pipes and/or boiler).
CLEANING YOUR BOILER AND BURNERS
Flue passages between sections should be examined 
yearly and cleaned if necessary. 
To clean: 
• Remove burners, pilot, and vent pipe.
• Remove top and front jacket panels. 
• Remove two screws attaching intermediate front 
panel to left and right side jacket panels. 
• Remove draft diverter and intermediate front panel 
as a unit. 
• Carefully remove cerafelt gasket strips. 
• Clean passageways between sections with flexible 
handle wire brush. Remove dirt from bottom of 
boiler and from between sections by vacuuming. 
• Verify all flame ports in burners are open and 
clear. Shake out or blow out all loose dirt in 
burners. 
• Reseal seams between adjacent sections as 
necessary with 400
°
 F RTV silicone sealant. 
• Reassemble all parts. 
• Verify tightness of pilot connections and condition 
of burner flames after reassembly. See Figures 16 
and 17, page 21. 
• Verify vent pipe connections to chimney are secure 
and no obstructions are present.
HOUSEKEEPING
• Keep boiler area clear and free from combustible 
materials, gasoline and other flammable vapors 
and liquids.
• Keep boiler area clear of debris and other 
materials obstructing flow of combustion and 
ventilation air.