Utica Boilers CuB Series 安装指导

下载
页码 48
17
6 - COMBUSTION AIR AND VENT PIPING OF DIRECT VENT AND CATEGORY III
Induced Draft Boilers
Horizontal (Category III) venting systems installation 
shall conform to the requirements of the authority having 
jurisdiction or, in the absence of such requirements, to 
the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and/
or Natural Gas and Propane Installation Code, CAN/CSA 
B149.1
1. 
Boilers may be vented horizontally.
 
Vent pipe is pitched 
down from boiler to vent termination. Do not connect 
other appliances to this vent. 
2. 
Vent Pipe Material UL Listed - AL294C Stainless Steel 
vent pipe and fi ttings.
3. 
Clearance to Combustible Materials: For stainless steel 
vent pipe maintain 6” minimum air space clearance to 
combustible materials.
4. 
Vent Pipe Size: 3” vent pipe connected directly to the 
outlet of the induced draft blower.
5. 
Vent Pipe Length:
A.  For stainless steel vent pipe, the maximum 
horizontal vent length is 65 equivalent feet. 
B.  Minimum horizontal vent length is 5 equivalent 
feet.
C.  For  3”  90° elbows = 5 equivalent feet of vent 
length.
6. 
Vent Termination Fitting: For all vent pipe materials, 
you may use either:
A.  90° elbow pointing down, fi tted with a minimum 
1/4” mesh screen to keep out rodents and birds. 
The elbow shall be of the same material and size 
as vent pipe. The elbow exit should be at least 6” 
away from exterior wall. 
-or-
B.  Concentric side wall vent hood. 
7. 
Vent Pipe Termination Location  :
A.  When venting through combustible walls, 
combustible clearances must be considered. ECR 
vent termination, 5612601, is a certifi ed direct vent 
termination (for Catagory III venting)  providing 
both the outside vent termination and a double 
wall pipe for passing through a combustible 
wall up to 10” thick. Vent terminations by other 
manufacturers may also be used as long as they 
are certifi ed for catagory III venting.
B.  If the 90° elbow is the termination fi tting of choice, 
then the single wall pipe will be passing through the 
side wall. For combustible walls, a UL listed thimble 
shall be used where the single wall pipe passes 
through the wall.
C.  For single wall pipe through non-combustible 
walls, the hole through the wall need only be large 
enough to maintain the pitch of the vent pipe, and 
provide proper sealing. A thimble is not required for 
single wall pipe passing through non-combustible 
walls.
D.  The venting system shall terminate at least 3 feet 
0.9m) above any forced air inlet located within 
10 feet (3m). The venting system shall terminate 
at least 4 feet (1.2m) below, 4 feet (1.2m) 
horizontally from, or 1 foot (300 mm) above any 
door, window, or gravity air inlet into any building. 
The bottom of the vent shall be located at least 12 
inches (300mm) above grade. Termination of the 
vent shall be not less than 7 feet (2.13m) above 
adjacent public walkway. The vent terminal shall 
not be installed closer than 3 feet (0.9m) from the 
inside corner of an L shaped structure. Termination 
of the vent should be kept at least 3 feet (0.9m) 
away from vegetation. The venting system shall 
terminate at least 4 feet horizontally from, and in 
no case above or below, unless a 4 foot horizontal 
distance is maintained, from electric meters, gas 
meters, regulators, and relief equipment. 
• The venting system shall terminate at least 4 feet 
below any eave, soffi t, or roof overhang.
• The venting system shall not terminate 
underneath any deck, patio, or similar structure.
• Put vent on a wall away from the prevailing 
winter wind. Locate or guard the vent to prevent 
accidental contact with people or pets.
• Terminate the vent above normal snow-line. Avoid 
locations where snow may drift and block the 
vent. Ice or snow may cause the boiler to shut 
down if the vent becomes obstructed.
• Under certain conditions, fl ue gas will condense, 
forming moisture. In such cases, steps should be 
taken to prevent building materials at the vent 
terminal from being damaged by exhaust of fl ue 
gas.
United States - Terminate vent system at least 
4 feet (1.22m) horizontally from, and in no case 
above or below, unless a 4 feet (1.22m) horizontal 
distance is maintained, from electric meters, gas 
meters, regulators and relief equipment.
Canada - Terminate vent system at least 6 feet 
(1.83 m) horizontally from, and in no case above 
or below, unless a 6 feet (1.83m) horizontal 
distance is maintained, from electric meters, gas 
meters, regulators and relief equipment.
8. 
Joining and Sealing the Vent Pipe: The vent pipe needs 
to be both watertight and gas tight. Seal all joints and 
seams following vent pipe manufacture’s installation 
instructions.
9. 
Support Spacing: Do not restrict thermal expansion 
movement of the vent. The vent pipe must expand 
and contract freely with temperature change. Each run 
of vent piping shall be supported following vent pipe 
manufacture’s instructions.