Utica Boilers CuB Series 安装指导

下载
页码 48
  
 WARNING
Asphyxiation hazard. Carbon monoxide is odorless, 
tasteless, clear colorless gas, which is highly toxic. 
Carbon monoxide production shall not exceed 
400ppm. Failure to follow these instructions could 
result in death or serious injury.
  
 WARNING
Asphyxiation hazard. Verify cap is fi rmly placed on 
combustion analyzer port to prevent CO emission. 
Failure to do so could result in death or serious 
injury.
9.3  Burner Pressure Adjustment
Unit has fl ame modulation, with two fi xed pressure values: 
minimum and maximum. See Sec. 12, page 34.
Connect pressure gauge to pressure point “B” downstream 
of the gas valve.
1. 
Remove protection cap “D”.
2. 
Operate boiler in TEST mode.
3. 
Adjust maximum pressure by turning screw “G” 
clockwise
 
 to increase pressure and counter clockwise 
 
to decrease.
4. 
Disconnect one of two connectors “C” from modulation 
regulator “F” on the gas valve.
5. 
Adjust minimum pressure by turning screw “E” clockwise 
 to increase the pressure and counter clockwise 
 to 
decrease it.
6. 
Turn burner on and off, verify minimum pressure 
remains stable.
7. 
Reconnect connector “C” detached from modulation 
regulator “F” on the gas valve.
8. 
Verify maximum pressure has not changed.
9. 
Replace protection cap “D”.
10. 
To end TEST mode, repeat activation sequence or wait 
15 minutes.
9.4 To Enter Test Mode/Adjust Heating Power 
Press CH+/- buttons at the same time for 5 seconds.
• 3 way valve is in CH position and burner is forced at 
100%.  Boiler automatically exits test mode after 15 
minutes or to exit test mode manually press CH +/- 
buttons together for 5 seconds.
• With Ch +/- buttons you can adjust Max power from (0 
to 100%)
9.5 Ignition Adjustment
To adjust ignition, switch boiler to TEST mode (See Start 
up Procedure). Press DHW buttons  to increase or decrease 
power (min.= 00,  max. = 60). Press RESET button within 
5 seconds and ignition remains set. Exit TEST mode.
24
9 - START UP PROCEDURE
9.1 Fill Boiler With Water And Purge Air
NOTICE
To maintain boiler effi ciency and prevent boiling 
inside the heat exchanger, fl ush entire heating 
system until clean. 
• Flush heating system, including all heating zones.
• Fill boiler with potable water.
• Fill boiler and system piping with water (or 
antifreeze-water solution, if used).  See antifreeze 
information Section 5.3 page 11.  Purge air from 
boiler using air vent.  Purge air from system piping.
• Inspect system piping and boiler connections.  
Repair any leaks immediately.
• Activate all heating zones and calls for heat, 
including CH calls and DHW calls (if available).
• Close manual gas shut off valve. Let system run for 
30 minutes. When boiler goes into lockout, reset 
boiler by pressing “Reset” button until boiler resets.
• Do not open gas shutoff valve until all air is purged 
from system.
9.2 Boiler Start-up and Operational Test
1. 
Verify air is purged from hydronic piping
2. 
System test pumps - verify each pump is 
operational
3. 
Verify gas piping
• Confi rm pressure test.  See section 7.3 page 20.
• Visually inspect piping to determine there are no 
open fi ttings or ends, and all valves at unused 
outlets are closed and plugged/capped.
• Purge air from piping
• Check piping and connections for leaks immediately 
after gas is turned on.  Shut off gas supply and 
make necessary repairs if leaks found.
4. 
Follow OPERATING INSTRUCTIONS to initiate boiler 
operation. See section 10.
5. 
Inspect combustion air and vent piping. Verify pipe 
is not leaking and terminations are unobstructed and 
vent gas discharge is not a nuisance or hazard.
6. 
Verify boiler operates.
7. 
Check control module operation.
8. 
Check fi eld sourced limits, low water cutoffs, etc. per 
manufacturer's instructions.