Utica Boilers JE 安装指导
14
Base Assembly
300, 400 and 500 boilers are the basic models.
300, 400 and 500 boilers are the basic models.
• 300 model has (6) burners
• 400 model has (8) burners
• 500 model has (10) burners
• 400 model has (8) burners
• 500 model has (10) burners
Combinations of basic models are used to assemble 600
through 1500 models.
Refer to Chart 3 for proper order of assembly. When two or
Refer to Chart 3 for proper order of assembly. When two or
more bases are used to assemble boiler, verify tops of bases
are even.
1.
Fasten bases together with 5/16 cap bolts and nuts.
2.
Insert two bolts in front posts and two in rear posts as
shown in Figure 7A .
3.
After bases are fastened, install base end panels.
Install end panels before assembling sections. See
Figure 7B.
NOTICE
Verify bases are level after assembly.
Section Assembly
1.
Start sections from left or right end of base.
2.
Place end section on base with center-line of section
directly over joint of base end closure.
3.
With boilers having two or more bases, as you progress
be sure parting line (center-line of section) of intermediate
sections fall on junction of two bases. See Figure 8.
Figure #7A
Bolts with nuts in
the front and rear
posts
INSTALLATION – ASSEMBLY
Figure 7A
Figure 7B
Alignment
of section
along side
Figure 8
Note: First
Section Alignment
is critical. Use side
of base to align
first section. Do
not allow side to
overhang base.