Acquisition and Storage of Curve Values 
For  the  displayed  course  to  reflect  the  actual  course,  the  sampling  rate  of  the  process 
value  has  to  correspond  at  least  to  twice  the  change  frequency  of  the  process  value.  In 
most cases, this requirement can be met with cyclical acquisition every 1s [2]. 
In  PCS 7,  the  sampling  rate  corresponds  to  the  acquisition  cycle  of  a  process  value.  As 
long  as  a  process  value  is  not  archive,  only  the  pre-history  of  the  process  value  can  be 
displayed.  By  archiving  a  process  value  (refer  to  chapter  P02-03)  the  history  can  be 
displayed also, since archive variables are resorted to. 
When curves are displayed, the pre-history differs from the history as shown in Table 1. 
Table 1: Visible Differences between Prehistory and History [2] 
 
Prehistory 
History 
Position of the time span 
shown in the curve field 
Always relative to the 
present 
Through an absolute point 
in time and a selected time 
span or through two 
absolute points in time 
Labeling of the time axis 
Relative time indications; if 
needed, can be switched to 
absolute time indication 
Absolute time indications 
can be switched to time 
indications relative to a 
defined point in time of an 
event  
Updates 
Curve is updated during the 
display whereby all curve 
points are shifted  
Curve does not change 
Value axis 
The value axis is usually 
located at the point in time of 
the present (at the right 
margin of the display) 
The value axis is located on 
the left margin of the display 
 
Designing Curve Displays 
In  [2],  guidelines  for  designing  curve  displays  are  provided.  PCS  7  implements  the  basic 
design  details  by  default;  for  that  reason,  they  are  described  here  only  briefly.  There  are 
design  rules,  however,  that  you  can  implement  yourself  by  means  of  the  settings  at  OS 
engineering. To do this in a specific way, a few details are introduced here. 
The curve display is displayed in the working area of the display area  (refer to P02-01). It 
consists of the  title field, the curve labeling field, and  the curve field. The title field should 
contain the information for the unambiguous assignment to the process environment. In the 
curve labeling field, it should be possible to read off the relationship of displayed  the curve 
and the process value. The curve display field is used to display the curve and should be 
as  large  as  possible.  To  implement  the  curve  display  field,  the  following  information  is 
provided. 
To  facilitate  reading  off  the  values,  grid  lines  have  to  be  available.  The  value  axis  in  this 
case  should  display  several  lines  as  an  extension  of  the  scale  marks,  and  the  time  axis 
several lines according to the current time grid. The number of grid lines should be low and 
optically remain in the background. To this end, they should not be shown in color or blue. 
Reading rulers can provide additional support.