Product Overview 
Siemens Building Technologies, Inc. 
 
Digital 
Application 
• Compressor 
2583 
•  Compressor 2 (optional); or stage 3 electric heat (optional) 
2583 
•  Compressor 3 (optional); or stage 2 electric heat (optional) 
2583 
•  Stage 1 electric heat (optional) 
2583, 2584 
• Reversing 
valve 
2583 
•  Damper actuator (floating control) (optional) 
2583, 2584 
• Fan 
2583, 2584 
•  Stage 1 cooling compressor (optional) 
2584 
•  Stage 2 cooling compressor (optional) 
2584 
•  Stage 1 heating compressor (optional) 
2584 
•  Stage 2 heating compressor (optional) 
2584 
Power Wiring 
The controller is powered by 24 Vac. Power wiring connects to terminals on the controller 
labeled “C” (Common) and “H” (Hot). An earth ground termination is also present. See Figure 
3.  
Communication Wiring 
The controller connects to the field panel by means of a Field Level Network (FLN) trunk. See 
Figure 4. 
C  H  EGRND WHEN THIRD TER-
MINATION IS PRESENT
24 V COMMON
24 V HOT
E GRND
POWER TRUNK
TEC0471R2
 
TEC0528R1
TWISTED PAIR
3-WIRE FLN TRUNK
SHIELD
WIRENUT
REFERENCE
IS NOT SHIELD
REFERENCE CONNECTION ABSENT 
IF 2-WIRE CABLE MUST BE USED
REFERENCE (EQUIPOTENTIAL)
GROUNDED AT SINGLE LOCATION 
TYPICALLY AT FIELD PANEL
Figure 3.  Power Wiring. 
Figure 4.  Communication Wiring.