Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual 
24  
Siemens Building Technologies, Inc. 
Description Address  Application 
Description 
CYCLE FAN 
60 
2583, 2584 
YES indicates that the fan should cycle ON and OFF with 
the compressor during day mode. NO indicates that the fan 
should remain ON constantly in day mode. 
Valid input: YES or NO 
NOTE:
 In either case, the fan will cycle during night mode. 
FREE CLG ON 
61 
2583, 2584 
Value, in percent, that the cooling loopout must exceed for 
free cooling to turn ON. 
FREE CLG OFF 
62 
2583, 2584 
Value, in percent, that the cooling loopout must exceed for 
free cooling to turn OFF. 
CLG P GAIN 
63 
2583, 2584 
Proportional gain value for the cooling temperature control 
loop. 
CLG I GAIN 
64 
2583, 2584 
Integral gain value for the cooling temperature control loop. 
STPT SPAN 
65 
2583, 2584 
Used to configure the allowable temperature range when 
using the optional Relative Setpoint Adjustment feature. 
STAT TYPE 
66 
2583, 2584 
Default = NORMAL. Can be set to OFFSET for optional 
Relative Setpoint Adjustment feature when room sensor part 
number SB1-0916 or SB1-1072 is used. 
Valid input: NORMAL or OFFSET 
HTG P GAIN 
67 
2583, 2584 
Proportional gain value for the heating temperature control 
loop. 
HTG I GAIN 
68 
2583, 2584 
Integral gain value for the heating temperature control loop. 
HP DO OVRD 
69 
2583, 2584 
For the commanding of critical digital outputs. CAUTION: 
IMPROPER USE CAN CAUSE PERMANENT EQUIPMENT 
DAMAGE. 
STPT OFFSET 
{70} 
2583, 2584 
For use with optional Relative Setpoint Adjustment feature. 
MA P GAIN 
{71} 
2583, 2584 
Proportional gain value for the mixed air control loop. 
MA I GAIN 
{72} 
2583, 2584 
Integral gain value for the mixed air control loop. 
MA D GAIN 
{73} 
2583, 2584 
Derivative gain value for the mixed air control loop. 
MA BIAS 
{74} 
2583, 2584 
Biasing of the mixed air control loop. 
CMP TOTL 
75 
2583 
Number of compressors used by the application.  
Valid values: 0123 
HTG CMP TOTL 
75 
2584 
Number of heating compressors used by the application. 
Valid values: 012 
EHTG STG CNT 
76 
2583, 2584 
Number of electric heating stages used by the application. 
Valid values: 0123 
CLG CMP TOTL 
77 
2584 
Number of cooling compressors used by the application. 
Valid values: 012 
CTL TEMP 
{78} 
2583, 2584, 2590 
Temperature used as input for the temperature  
control loops. This value will be the same as the value in 
ROOM TEMP + RMTMP OFFSET unless it is overridden. 
CLG LOOPOUT 
{79} 
2583, 2584 
Cooling temperature control loop output value in percent.