User Guide: LDRA6 
Chapter 4: Start-Up 
15 970 
484-6510 
www.rletech.com 
4-3.10  t – Toggle Modbus Trace On/Off 
will toggle Modbus tracing with packet viewing from the RS485 port over the RS232 port.  This is a 
command for advanced diagnostic purposes only. 
4-3.11  z – Display Leak Zone Readings 
will display the present Leak Detection Cable readings.  The Leak Zone table will display the reading for 
each leg of cable and the present leakage current reading for each zone. 
 
 
 
4-3.12  sr – summary relay mode 
sr will display the current configuration of the summary relay.  You can select the summary relay to either 
change state on leak/fault or just a fault condition.  Enter, sr <space> summary for notification on a 
leak/fault condition.    Enter, sr <space> fault for notification on a fault condition.     
 
 
4-3.13  zr – zone relay mode  
zr will display the current configuration of the zone relays.  You can select the zone relays to either change 
state on leak/fault (summary) or just a leak condition.  Enter, zr <space> summary for notification on a 
leak/fault condition.    Enter, zr <space> leak for notification on a leak condition.     
 
 
4-3.14  x – Exit to Bootloader 
x will exit the application code and only the bootloader will be running. 
zr 
zr/summary (summary/leak) 
zr leak 
zr/leak (summary/leak) 
sr 
sr/summary (summary/fault) 
sr fault 
sr/fault (summary/fault) 
Z1: Leg1: 0    Leg2: 0    Leakage: 0 
Z2: Leg1: 0    Leg2: 0    Leakage: 0 
Z3: Leg1: 0    Leg2: 0    Leakage: 0 
Z4: Leg1: 0    Leg2: 0    Leakage: 0 
Z5: Leg1: 0    Leg2: 0    Leakage: 0 
Z6: Leg1: 0    Leg2: 0    Leakage: 0